Options, Protective features – Rockwell Automation 1336T FORCE Series B User Manual

Page 15

Advertising
background image

Chapter 1
Introduction

1–3

Encoderless Speed Regulation – 1% of Top Speed over a 40:1 Speed
Range.

Accel/Decel – Independently programmable accel and decel times.
Program from 0 to 6553 seconds in 0.1 second increments.

Current Limit – Independent Motoring and Regenerative Limit

Inverse Time Overload Capability – Class 20 protection with
speed–sensitive response. Adjustable from 0–200% of rated output
current in 3 speed ranges – 2:1, 4:1 & 10:1. UL Certified – Meets
NEC Article 430.

Options

Standard Adapter Board which provides:
– 2 Analog Inputs +/–10V
– 2 Analog Outputs +/– 10V
– One 4–20mA input
– One 4–20mA output
– 5 or 12 vdc pulse input
– +/– 10V reference voltages
– At Speed, Run, Fault and Alarm contacts

PLC Communication Adapter Board which provides:
– 4 Analog Inputs +/–10V
– 4 Analog Outputs +/– 10V
– +/– 10V Reference voltages
– RIO/DH

TM

+ Communications (2 channels selectable)

– Function Blocks

DriveTools

TM;

PC Windows

TM

based programming software

compatible with the 1336 FORCE Drive and also other
Allen–Bradley 1336 and 1395 products.

Dynamic Braking

AC Motor Contactor

Protective Features

The 1336 FORCE Drive incorporates the following protective measures:

Programmable Motor Overload Protection (I

2

T) investigated by UL

to comply with NEC Article 430.

Programmable Inverter Overload Protection (IT)

Overspeed Detection, even when operating as a torque follower.

Programmable Stall Detection

Peak output current monitoring to protect against excessive current
at the output due to a phase to ground or phase to phase short.

Ground fault monitoring

DC Bus Voltage monitoring to protect against under/over voltage
conditions.

Power Structure Heatsink Temperature Monitoring