Rockwell Automation 1336T FORCE Series B User Manual

Page 168

Advertising
background image

Chapter 5
Programming Parameters

5–42

Powerup/Diagnostic Fault Status
[PwrUp Flt Status]

Parameter Number

80

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Enums:

This word parameter indicates a fault
condition which has been detected during
power up or reset of the drive. When a bit
is “1”, the condition is true, otherwise the
condition is false.

Bit

Condition

0

CP PROM Failure

1

CP Internal RAM Failure

2

CP External RAM Failure

3

CP Stack RAM Failure

4

VP Dualport RAM Failure detected by CP

5

Not Used

6

Not Used

7

Not Used

8

VP EPROM Failure

Bit

Condition

9

VP Internal RAM Failure

10

VP External RAM Failure

11

VP Stack RAM Failure

12

CP Dualport RAM Failure detected by VP

13

AP Dualport Ram Failure detected by VP

14

Base Drive EE Failure

15

Reserved, Leave Zero

CP Configurable Fault Status
[CP Flt Status]

Parameter Number

82

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Enums:

This word parameter indicates conditions
detected by the Current Processor (CP)
that has been configured to report as a
Drive fault condition. Each configuration
bit matches the bit definitions of Parameter
84, 86 and 87. When a bit is “1” the
condition is true, otherwise the condition is
false.

Non–configurable Fault Status
[Ncfg Flt Status]

Parameter Number

81

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Enums:

This word parameter indicates fault condi-
tions in the drive that Cannot be configured
as warnings. When a bit is “1”, the condi-
tion is true, otherwise the condition is false.
Bits 0 – 3 are detected by hardware. Bits
4–15 are detected by software.

Bit

Condition

0

DC Bus Overvoltage Trip

1

Transistor Desaturation

2

Ground Fault

3

Instantaneous Overcurrent

4

Adapter Comm Loss detected by CP

5

Master/Slave Cable Loss

Bit

Condition

0

Bus Ridethrough Timeout

1

Bus Precharge Timeout

2

Bus Drop (150 volts)

Bit

Condition

10

Analog Power Supply Tolerance

11

Autocommisioning or Transistor Diagnostic Failure

12

Inverter Temperature Trip

13

Software Malfunction detected by VP

14

Not Used

15

Reserved, Leave Zero

Bit

Condition

3

Bus Undervoltage

4

Bus Drop Cycles > 5

5

Fast Fluxup Current < 50%

Bit

Condition

6

Master/Slave Enable Timeout

7

Not Used

8

Handshake Timeout VP

9

Absolute Overspeed

VP Configurable Fault Status
[VP Flt Status]

Parameter Number

83

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Enums:

This word parameter indicates conditions
detected by the Velocity Processor (VP)
that have been configured to report as fault
conditions. Each configuration bit matches
the definitions of Parameter 85, 88 and 89.
When a bit is “1” the condition is true,
otherwise the condition is false.

Bit

Condition

0

Feedback Loss

1

Inverter Overtemp Pending

2

Motor Overtemperature Tripped

3

Motor Overload Pending

4

Motor Overload Trip

Bit

Condition

10

Math Limit

11

Dynamic Brake Overtemperature

12

AC Motor Contactor Failure

13

Inverter Overload Pending (IT)

14

Drive to Drive Communication Fault

15

Inverter Overload Trip (IT)

Bit

Condition

5

Motor stalled

6

External Fault

7

RMS Fault

8

Not Used

9

Parameter Limit

Advertising