Chapter 5
Programming Parameters

5–39

Torque Stop Configuration
[Torq Stop Config]

Parameter Number

58

Parameter Type

Sink

Display Units

x

Drive Units

None

Factory Default

0

Minimum Value

0

Maximum Value

2

Enums:

This parameter selects how the drive will
react to a stop command when it occurs in
a non–speed mode (ex. torque mode).
Possible selections are:
0 = Normal Mode – Switch to speed mode.
then perform a controlled stop.
1 = Stay in selected torque mode until zero
speed is reached.
2 = Stay in selected torque mode until zero
torque is reached.

At Setpoint 1
[At Setpoint 1]

Parameter Number

60

Parameter Type

Sink

Display Units

+/– x.x %

Drive Units

4096 = 100.0% setpoint

Factory Default

+0.0%

Minimum Value

– 800.0%

Maximum Value

+ 800.0%

At Setpoint 2
[At Setpoint 2]

Parameter Number

61

Parameter Type

Sink

Display Units

+/– x.x%

Drive Units

4096 = 100.0% setpoint

Factory Default

+0.0%

Minimum Value

–800.0%

Maximum Value

+800.0%

This parameter is used to specify the
setpoint threshold for the At Setpoint
1 bit in Logic Status Hi.

This parameter is used to specify the
setpoint threshold for the At Setpoint
2 bit in Logic Status Hi.

Logic Options
[Logic Options]

Parameter Number

59

Parameter Type

Sink

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0001 0010

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Enums:

This parameter selects the options for logic
operation of the drive as follows:

bit#

Option

0

Start Type A*

1

Start Type B*

2

Jog Ramp Enable

3

= 1 / Jog Coast
= 0 / Regen Stop

4

STOP Input Type A**

5

STOP Input Type B**

6

Do Power Up Diag.

7

Do Flux Up Diag

8

Do Start Diag

9

Not Used

10

Not Used

11

= 1 / AC Motor Contactor Present

12

= 1 / Bipolar Ref +ref value = Forward Dir.

– ref value = Reverse Dir.

= 0 / Unipolar Bit 4 of P52 = 1,
Forward Direction
Bit 5 of P52 = 1 , Reverse Direction

Over Setpoint 2
[Over Setpoint 2]

Parameter Number

63

Parameter Type

Sink

Display Units

+/– x.x%

Drive Units

4096 = 100% setpoint

Factory Default

+ 0.0%

Minimum Value

–800.0%

Maximum Value

+800.0%

This parameter is used to specify the set-
point threshold for the Over Setpoint 2 bit
in Logic Status Hi.

Over Setpoint 1
[Over Setpoint 1]

Parameter Number

62

Parameter Type

Sink

Display Units

+/– x.x%

Drive Units

4096 = 100% setpoint

Factory Default

+0%

Minimum Value

–800.0%

Maximum Value

+800.0%

This parameter is used to specify the
setpoint threshold for the Over Setpoint 1
bit in Logic Status Hi.

* Start Type
B

A

0

0

Maint. Start, Rgen Stop

0

1

Maint. Start, Coast Stop

1

0

Momentary Start

1

1

Maint. Start, Rgen Stop

** Stop Type
B

A

0

0

Coast

0

1

Normal (Ramp–Regen)

1

0

I - Limit

1

1

Coast

This parameter has no effect if the drive is
already in speed mode when a stop com-
mand occurs. Coast stop

1

commands are

also unaffected by this parameter.

1

NOTE: Coast indicates that the Inverter

power has been disabled, but actual rotational
stoppage of the motor is dependent on the
friction of the connected load.