Chapter 5
Programming Parameters

5–43

CP Configurable Warning Status
[CP Warn Status]

Parameter Number

84

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Enums:

VP Configurable Warning Status (bits)
[VP Warn Status]

Parameter Number

85

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Enums:

This word parameter indicates conditions
detected by the current processor (CP) that
have been configured to report as a Drive
Warning condition. Each configuration bit
matches the bit definitions of parameters
82, 86 and 87. When a bit is set to “1” the
corresponding condition in the Drive is
true, otherwise it is false.

This word parameter indicates conditions
detected by the Velocity Processor (VP)
that have been configured to report as a
Drive warning condition. Each configura-
tion bit matches the bit definitions of
parameters 83, 88 and 89. When a bit is
set to “1”, the corresponding condition in
the Drive is true, otherwise it is false.

Bit

Condition

0

Bus Ridethrough Timeout

1

Bus Precharge Timeout

2

Bus Drop

3

Bus Undervoltage

4

Bus Drop Cycles > 5

5

Fast Flux Up Current < 50%

Bit

Condition

0

Encoder Feedback Loss

1

Inverter Overtemp Pending

2

Motor Overtemperature Tripped

3

Motor Overload Pending (I

2

T)

4

Motor Overload Trip (I

2

T)

5

Motor Stalled

6

External Fault

7

RMS Fault

8

Not Used

9

Parameter Limit

10

Math Limit

Bit

Condition

11

Dynamic Brake Resistor Overtemperature

12

Motor Contactor Failure

13

Inverter Overload Pending (IT)

14

Drive to Drive Communication Fault

15

Inverter Overload Foldback

CP Fault/Warning Configuration Select
[CP Fault Select]

Parameter Number

86

Parameter Type

Sink

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0010 0011

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Enums:

This word parameter determines conditions
detected by the Current Processor (CP)
that will be reported as either a drive fault
or drive warning condition. Each configu-
ration bit matches the bit definitions of
parameters 82, 84 and 87. When a bit is
set to ”1”, the corresponding condition in
the Drive will be reported as a FAULT,
otherwise it will be reported as a
WARNING.

Bit

Condition

0

Bus Ridethrough Timeout

1

Bus Precharge Timeout

2

Bus Drop

3

Bus Undervoltage

4

Bus Drop Cycles > 5

5

Fast Flux Up Current < 50%

Advertising