Chapter 5
Programming Parameters

5–78

Milli Amp Input Offset
[mA Input Offset]

Parameter Number

362

Parameter Type

Sink

Display Units

+ x.xxx mA

Drive Units

128 = 1mA

Factory Default

+0.000 mA

Minimum Value

–32.000 mA

Maximum Value

+32.000 mA

This parameter determines the offset ap-
plied to the raw analog value of the milli
amp input before the scale factor is ap-
plied. This allows the user to shift the
range of the analog input.

Milli Amp Input Scale
[mA Input Scale]

Parameter Number

363

Parameter Type

Sink

Display Units

+/– x.xxx

Drive Units

2048 = 1

Factory Default

+2.000

Minimum Value

–16.000

Maximum Value

+16.000

This parameter determines the scale factor
or gain for the milli amp input. The milli
amp input is converted to a +/– 2048 and
then the scale is applied which allows an
effective digital range of +/– 32767.

SCANport Analog1 Select
[SB Analog Sel]

Parameter Number

364

Parameter Type

Sink

Display Units

x

Drive Units

None

Factory Default

1

Minimum Value

1

Maximum Value

6

Enums:

This parameter selects which SCANport
analog device is used in parameter 365
‘SP Analog In’.

1

SCANport 1

2

SCANport 2

3

SCANport 3

4

SCANport 4

5

SCANport 5

6

SCANport 6

SCANport Analog1 In
[SB Analog1 In]

Parameter Number

365

Parameter Type

Source

Display Units

+/– x

Drive Units

None

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

This parameter displays the analog value
of the SCANport device selected in
parameter 364 ‘SP Analog Sel’.

SP Analog1 Scale
[SB Analog1 Scale]

Parameter Number

366

Parameter Type

Sink

Display Units

+/–x

Drive Units

+/– 1, 1 = 32767

Factory Default

1 (32767)

Minimum Value

–1 (–32767)

Maximum Value

1 (32767)

This parameter can be used to scale the
value in Parameter 365.

Advertising