Chapter 6
Troubleshooting

6–18

Figure 6.6
Parameter 83 (VP Configurable Fault Status)

Feedback Loss

Inverter Overtemp Pending

Motor Overtemperature Tripped

Motor Overload Pending – IIT

Motor Overload Trip – IIT

Motor Stalled

External Fault

RMS Fault

NOT USED

Parameter Limit

Math Limit

Dynamic Brake Resistor Overtemperature

AC Motor Contactor Failure

Inverter Overload Pending (IT)

Drive–to–Drive Communication Fault

Inverter Overload Trip (IT)

O O O O O O O O. O O O O O O O O

Bit#

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Figure 6.7
Parameter 89 (VP Warning/None Configuration Select (bits))

O O O O O O O O. O O O O O O O O

Bit#

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

This word parameter indicates conditions detected by the Velocity Processor (VP) that have been configured to report as
a Drive fault condition. Each configuration bit matches the bit definitions of Parameters 85, 88 and 89. When a bit is set
to “1”, the corresponding condition in the Drive is true, otherwise the condition is false.

Feedback Loss

Inverter Overtemp Pending

Motor Overtemperature Tripped

Motor Overload Pending – IIT

Motor Overload Trip – IIT

Motor Stalled

External Fault

RMS Fault

NOT USED

Parameter Limit

Math Limit

Dynamic Brake Resistor Overtemperature

AC Motor Contactor Failure

Inverter Overload Pending (IT)

Drive–to–Drive Communication Fault

Inverter Overload Foldback (IT)

This word parameter indicates conditions detected by the Velocity Processor (VP) that will be reported as either a drive
fault or warning or not reported at all (ignored). Each configuration bit matches the bit definitions of Parameters 83, 85
and 88. When a bit is set to “1”, the corresponding condition in the Drive will be reported as configured by parameter 88.
When the bit is set to “0”, the condition is not reported.