Rockwell Automation 1336T FORCE Series B User Manual

Page 161

Advertising
background image

Chapter 5
Programming Parameters

5–35

Process Trim KP Gain
[Proc Trim Kp ]

Process Trim Low Limit
[Proc Trim Lo Lmt]

Process Trim High Limit
[Proc Trim Hi Lmt]

Parameter Number

35

Parameter Type

Sink

Display Units

+/– x.x%

Drive Units

4096 = 100% trim

Factory Default

– 100%

Minimum Value

– 800%

Maximum Value

+ 800%

Parameter Number

34

Parameter Type

Sink

Display Units

+/– x.x%

Drive Units

4096 = 100% trim

Factory Default

–100.0%

Minimum Value

–800.0%

Maximum Value

+800.0%

Process Trim Output Gain
[Proc Trim Out K]

Parameter Number

36

Parameter Type

Sink

Display Units

+/– x.xx

Drive Units

2048 = +1.00 gain

Factory Default

+ 1.00

Minimum Value

– 16.00

Maximum Value

+ 16.00

Parameter Number

37

Parameter Type

Source

Display Units

+/– x

Drive Units

None

Factory Default

+0

Minimum Value

–32767

Maximum Value

+32767

Parameter Number

33

Parameter Type

Sink

Display Units

x.xxx

Drive Units

4096 = 1.0000 Kp gain

Factory Default

1.000

Minimum Value

0.000

Maximum Value

16.000

Process Trim Testpoint
[Proc Trim TP]

This parameter controls the proportional
gain of the process trim regulator. If the
KP process trim is equal to 1.0, then the
process trim PI regulator output will equal 1
pu for 1 pu process trim error.

The output of the process trim regulator is
limited by adjustable high and low limits.
This parameter specifies the low limit of the
process trim output value.

The output of the process trim regulator is
limited by adjustable high and low limits.
This parameter specifies the high limit of
the process trim output value.

This parameter selects which location of
the Process Trim Controller will become
the testpoint value as follows:
Value

Process Trim Access Point

0

Zero

1

Process Trim Error

2

Process Trim Filter Output

3

Process Trim Control Word

The output of the process trim regulator is
scaled by a gain factor. This occurs just
before the upper and lower limit. This pa-
rameter specifies the gain value to use.

Process Trim Testpoint Select
[Proc Trim TP Sel]

This parameter indicates the value of the
internal location selected by the Process
Trim Testpoint Select parameter.

Parameter Number

38

Parameter Type

Sink

Display Units

x

Drive Units

None

Factory Default

0

Minimum Value

0

Maximum Value

3

Enums:

Auto Tune Torque Limit
[Auto Tune Torque]

Parameter Number

40

Parameter Type

Sink

Display Units

x.x %

Drive Units

4096 @ rated motor torque

Factory Default

50.0 %

Minimum Value

25.0 %

Maximum Value

100.0 %

This parameter specifies the motor torque
that is applied to the motor during the
Velocity motor test and the Velocity system
test. 4096 = 100% rated motor torque.

Advertising