Input/output ratings, Ac supply source – Rockwell Automation 1336T FORCE Series B User Manual

Page 28

Advertising
background image

Chapter 2
Installation/Wiring

2–8

Input/Output Ratings

The input and output current ratings grouped by drive voltage rating are
provided in the following table:

200–240V

Cat No.

A001
A003
A007
A010
A015
A020
A025
A030
A040
A050
A060
A075
A100
A125

Input
kVA

Input
Amps

2
4–5
10–12
12–14
17–20
23–28
25–30
27–30
43–51
53–64
60–72
82–99
100–120
111–134

5
12
28
35
49
67
73
79
123
154
174
238
289
322

Output
kVA

2
5
11
14
19
26
31
32
48
60
72
96
116
130

Output
Amps

4.5
12
27.2
33.7
48.2
64.5
78.2
80
120.3
149.2
180.4
240
291.4
327.4

380–480V

Cat No.

B001
B003
B007
B010
B015
B020
B025
B030
BX040
B040
B050
BX060
B060
B075
B100
B125
BX150
B150
B200
BX250
B250
B300
B350
B400
B450
B500
B600
BP250
BP300
BP350
BP400
BP450
B700C
B800C
12B700C
12B800C

Input
kVA

Input
Amps

2
4–5
9–12
14–18
18–23
23–29
23–26
32–41
40–50
41–52
48–60
62
61–77
78–99
98–124
117–148
148
157–198
191–241
231–291
212–268
265–335
300–379
330–416
372–470
391–494
439–555
230–291
265–334
300–378
313–396
346–437
517–625
647–817
517–625
647–817

3
6
14
22
28
35
43
49
62
63
75
75
93
119
149
178
178
238
290
350
322
403
455
501
565
594
668
350
402
455
476
526
835
965
835
965

Output
kVA

2
5
11
17
22
27
33
38
47
52
61
61
76
96
120
143
143
191
233
282
259
324
366
402
454
477
537
282
324
366
383
424
677
783
677
783

Output
Amps

2.5
6.0
13.9
20.9
27.2
33.7
41.8
48.2
58.7
64.5
78.2
78.2
96.9
120.3
149.2
180.4
180.4
240.0
291.4
353.6
327.4
406.4
459.2
505.1
570.2
599.2
673.4
353.6
406.4
459.2
481.0
531.7
850
983
850
983

575V

Cat No.

C001
C003
C007
C010
C015
C020
C025
C030
C040
C050
C060
C075
C100
C125
C150
C200
C250
C300
C350
C400
C450
C500
C600
C650
C700
C800
12C700C
12C800C

Input
kVA

Input
Amps

2–3
5–6
9–11
11–13
17–20
21–26
27–32
31–37
40–48
48–57
52–62
73–88
94–112
118–142
136–163
217–261
244–293
256–307
304–364
349–419
394–473
434–520
514–617
578–694
616–739
639–767
616–739
639–767

3
6
10
12
19
25
31
36
46
55
60
84
108
137
157
251
282
296
351
403
455
501
594
668
756
786
756
786

Output
kVA

2
6
10
12
19
24
30
35
45
57
62
85
109
137
157
251
283
297
352
405
457
503
597
671
767
797
767
797

Output
Amps

2.5
6
9.9
12
18.9
23.6
30
34.6
45.1
57.2
61.6
85.8
109.1
138.6
159.7
252.5
283.6
298
353.6
406.4
459.2
505.1
599.2
673.4
770
800
770
800

AC Supply Source

11–485 kW (7.5–650HP) drives are suitable for use on a circuit capable of
delivering up to a maximum of 200,000 rms symmetrical amperes, 600
volts maximum when used with the AC input line fuses specified in Table
2.A. The 1336 FORCE does not contain input power short circuit fusing.
Specifications for the recommended size and type to provide drive input
power protection against short circuits are on the following pages.

ATTENTION: To guard against personal injury and/or equipment
damage caused by improper fusing, use only the recommended
line fuses specified in Table 2.A. Branch circuit breakers or
disconnect switches cannot provide this level of protection for
drive components.

!