Rockwell Automation 1336T FORCE Series B User Manual

Page 184

Advertising
background image

Chapter 5
Programming Parameters

5–58

Perunit Motor Voltage
[Motor Volt Fdbk]

Displays the perunit value of motor voltage
as determined from an analog–to–digital
converter input. This data is scaled to read
1.0 pu at rated motor voltage. This is a
version of parameter 265 that has been
scaled to perunit to be compatible with
analog outputs. This data is averaged and
updated on a 50 millisecond basis.

Parameter Number

186

Parameter Type

Source

Display Units

x.x%

Drive Units

4096 = 100.0% motor voltage

Factory Default

0.0%

Minimum Value

0.0%

Maximum Value

800.0%

Rated Inverter Output Amps
[Base Drive Curr]

Parameter Number

220

Parameter Type

Source

Display Units

x.x amps

Drive Units

Display units x 10

Factory Default

20.0 amps

Minimum Value

0.1 amps

Maximum Value

3,276.7 amps

Current rating of inverter.
Automatically set by drive at powerup as a
function of Power Structure Type. Used for
current ref scaling and current processor
feedback scaling.

Rated Inverter Input Voltage
[Base Line Volt]

Parameter Number

221

Parameter Type

Source

Display Units

x volt

Drive Units

Non

Factory Default

460 volt

Minimum Value

75 volt

Maximum Value

575 volt

Drive Nameplate Voltage rating of inverter.
Automatically set by drive at powerup as a
function of Power Structure Type.

Inverter Carrier Frequency
[PWM Frequency]

Parameter Number

222

Parameter Type

Sink

Display Units

x Hz

Drive Units

None

Factory Default

4,000 Hz

Minimum Value

1,000 Hz

Maximum Value

12,000 Hz

This parameter defines the drive carrier
frequency in Hz.

Advertising