Ce conformity, Emc directive, Requirements for conforming installation – Rockwell Automation 1336T FORCE Series B User Manual

Page 303

Advertising
background image

Appendix

B

B–1

CE Conformity

EMC Directive

This apparatus is tested to meet Council Directive 89/336
Electromagnetic Compatibility (EMC) using a technical construction file
and the following standards:

EN 50081–1, –2 – Generic Emission Standard

EN 50082–1, –2 – Generic Immunity Standard

Marked for all applicable directives

1

Emissions

EN 50081-1
EN 50081-2
EN 55011 Class A
EN 55011 Class B

Immunity

EN 50082-1
EN 50082-2
IEC 801-1, 2, 3, 4, 6, 8 per EN50082-1, 2

Important:

The conformity of the drive and filter to any standard does
not guarantee that the entire installation will conform. Many
other factors can influence the total installation and only
direct measurements can verify total conformity.

The following seven items are required for CE conformance:

1. Standard 1336 FORCE Drive 0.37-45 kW (1-60 HP) CE compatible

(Series D or higher).

2. Factory installed EMC enclosure (-AE option) or field installed EMC

Enclosure Kit (1336x-AEx – see page B–2)

3. Filter as called out on the following page.

4. Grounding as shown on page B–2.

5. Maximum cable length (drive to motor) of 75 meters (250 feet).

6. Input power (source to filter) and output power (filter to drive & drive

to motor) wiring must be braided, shielded cable with a coverage of
75% or better, metal conduit or other with equivalent or better attenu-
ation, mounted with appropriate connectors. For shielded cable it is
recommended to use a compact strain relief connector with double
saddle clamp for filter and drive input and compact strain relief
connector with EMI protection for motor output.

7. Control (I/O) and signal wiring must be in conduit or have shielding

with equivalent attenuation.

Requirements for

Conforming Installation

Advertising