Chapter 5
Programming Parameters

5–75

SCANport Jog 1 Owner
[Jog 1 Owner]

Parameter Number

343

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000

Minimum Value

0000 0000

Maximum Value

0111 1111

Enums:

This parameter displays which SCANport
devices are presently issuing a valid jog 1
command.
1 = Jog 1 Input present
0 = Jog 1 Input Not Present

Bit 0 – TB3
Bit 1 – SCANport Device 1
Bit 2 – SCANport Device 2
Bit 3 – SCANport Device 3

Bit 4 – SCANport Device 4
Bit 5 – SCANport Device 5
Bit 6 – SCANport Device 6 (Int Gateway)
Bit 7 – Reserved, Leave Zero

SCANport Reference Owner
[Reference Owner]

Parameter Number

345

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000

Minimum Value

0000 0000

Maximum Value

0111 1111

Enums:

This parameter displays which SCANport
device currently has exclusive control of
the reference changes.
1 = Current Owner
0 = Non Owner

SCANport Jog 2 Owner
[Jog 2 Owner]

Parameter Number

344

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000

Minimum Value

0000 0000

Maximum Value

0111 1111

Enums:

This parameter displays which SCANport
devices are presently issuing a valid jog 2
command.
1 = Jog 2 Input Present
0 = Jog 2 Input Not Present

Bit 0 – TB3
Bit 1 – SCANport Device 1
Bit 2 – SCANport Device 2

Bit 3 – SCANport Device 3
Bit 4 – SCANport Device 4
Bit 5 – SCANport Device 5

Bit 6 – SCANport Device 6 (Int Gateway)
Bit 7 – Reserved, Leave Zero

Bit 0 – TB3
Bit 1 – SCANport Device 1
Bit 2 – SCANport Device 2

Bit 3 – SCANport Device 3
Bit 4 – SCANport Device 4
Bit 5 – SCANport Device 5

Bit 6 – SCANport Device 6 (Int Gateway)
Bit 7 – Reserved, Leavc Zero

SCANport Local Control Owner
[Local Owner]

Parameter Number

346

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000

Minimum Value

0000 0000

Maximum Value

0111 1111

Enums:

This parameter displays which SCANport
device currently has exclusive control of
the drive.
1 = Current Owner
0 = Non Owner

Bit 0 – TB3
Bit 1 – SCANport Device 1
Bit 2 – SCANport Device 2

Bit 3 – SCANport Device 3
Bit 4 – SCANport Device 4
Bit 5 – SCANport Device 5

Bit 6 – SCANport Device 6 (Int Gateway)
Bit 7 – Reserved, Leave Zero

SCANport Flux Owner
[Flux Owner]

Parameter Number

347

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000

Minimum Value

0000 0000

Maximum Value

0111 1111

Enums:

This parameter displays which SCANport
devices are presently issuing a valid flux
command.
1 = Flux Input Present
0 = Flux Input Not Present

Bit 0 – TB3
Bit 1 – SCANport Device 1
Bit 2 – SCANport Device 2

Bit 3 – SCANport Device 3
Bit 4 – SCANport Device 4
Bit 5 – SCANport Device 5

Bit 6 – SCANport Device 6 (Int Gateway)
Bit 7 – Reserved, Leave Zero