Chapter 2
Installation/Wiring

2–40

Figure 2.27.
Option L5/L5E Wiring

Typical

TB3

L5, L5E Options

A

A

ENC

RET

ENC

12V

Common

+24V

Typical

12V

681

100

90.9

5V

JP4

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

0.22

µ

f

1k

20k

510

510

510

User Supplied

24V AC/DC

Contacts shown are general, refer to Figures 2.24 & 2.25 for

Input Mode selection and recommended contact types.

NOT

USED

Option L5/L5E – 24V AC/DC Interface Board Requirements

Circuits used with Option L5/L5E must be capable of operating with high
= true logic.

DC external circuits in the low state must generate a voltage of no more
than 8V DC. Leakage current must be less than 1.5 mA into a 2.5k ohm
load.

AC external circuits in the low state must generate a voltage of no more
than 10V AC. Leakage current must be less than 2.5 mA into a 2.5k ohm
load.

Both AC and DC external circuits in the high state must generate a voltage
of +20 to +26 volts and source a current of approximately 10 mA for each
input.

The L5/L5E option is compatible with these Allen–Bradley PLC modules:

1771–OB

1771–OQ16

1771–OB16

1771–OBD

1771–OYL

1771–OBN

1771–OZL

1771–OQ

1771–OBB