Motor Inductance Test Errors
[Lo Test Error]

Parameter Number

295

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

This parameter indicates an error condition
detected during the motor inductance test.
1 = Drive condition true
0 = Drive condition false

Bits are defined as follows:
Bit

Condition

0

Motor Not at Zero Speed

1

Sign Error

2

Zero Current

3

A/D Overflow at min gain

4

Enable drop out

5

Sign error/Overflow

6 to 15

Reserved

Motor Stator Resistance Test Errors
[Rs Test Error]

Parameter Number

296

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Low frequency gain boost of the frequency
regulator in sensorless mode. This param-
eter must not be changed.

Bits are defined as follows:
Bit

Condition

0

Motor Not at Zero Speed

1

Sign Error

2

Not Used

3

Zero Current

4

Not Used

5

Software Error

6

Not Used

7

Enable Drop Out

8–15

Reserved

Motor Flux (Id) Test Errors
[Id Test Error]

Parameter Number

297

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

This parameter indicates an error condition
detected during the motor flux (Id) test. If a
bit is set to “1” the Drive condition is true,
otherwise the condition is false.

Torque Block Calculation Errors
[Torq Calc. Error]

Parameter Number

298

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Enums:

This word parameter indicates an error
condition which has been detected during
the torque block calculations. If a bit is set
to “1” the Drive condition is true, otherwise
the condition is false.

Bits are defined as:

Bit

Condition

0
1 to 15

Negative or Zero Slip
Reserved

Bits are defined as follows:
Bit

Condition

0

Autotune Speed Low (30% min)

1

Identified Id < zero

2

Identified Id > 100% motor current

3

Enable drop out

4–15

Reserved