Rockwell Automation 1336T FORCE Series B User Manual

Page 202

Advertising
background image

Chapter 5
Programming Parameters

5–76

SCANport Ramp Owner
[Ramp Owner]

Parameter Number

349

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000

Minimum Value

0000 0000

Maximum Value

0111 1111

Enums:

This parameter displays which SCANport
devices are presently issuing a valid ramp
command.
1 = Ramp Input Present
0 = Ramp Input Not Present

SCANport Clear Fault Owner
[Clr Fault Owner]

Parameter Number

350

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000

Minimum Value

0000 0000

Maximum Value

0111 1111

Enums:

This parameter displays which SCANport
devices are presently issuing a valid Clear
Fault Command.
1 = Clear Fault Input Present
0 = Clear Fault Input Not Present

Bit 0 – TB3
Bit 1 – SCANport Device 1
Bit 2 – SCANport Device 2

Bit 3 – SCANport Device 3
Bit 4 – SCANport Device 4
Bit 5 – SCANport Device 5

Bit 6 – SCANport Device 6 (Int Gateway)
Bit 7 – Reserved, Leave Zero

Bit 0 – TB3
Bit 1 – SCANport Device 1
Bit 2 – SCANport Device 2

Bit 3 – SCANport Device 3
Bit 4 – SCANport Device 4
Bit 5 – SCANport Device 5

Bit 6 – SCANport Device 6 (Int Gateway)
Bit 7 – Reserved, Leave Zero

SCANport Process Trim Owner
[Trim Owner]

Parameter Number

348

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000

Minimum Value

0000 0000

Maximum Value

0111 1111

Enums:

This parameter displays which SCANport
devices are currently issuing a valid
process trim command.
1 = Process Trim Input Present
0 = Process Trim Input Not Present

Bit 0 – TB3
Bit 1 – SCANport Device 1
Bit 2 – SCANport Device 2

Bit 3 – SCANport Device 3
Bit 4 – SCANport Device 4
Bit 5 – SCANport Device 5

Bit 6 – SCANport Device 6 (Int Gateway)
Bit 7 – Reserved, Leave Zero

10 Volt In Filtr
[10 Volt In Filtr]

Parameter Number

352

Parameter Type
Display Units

x.x r/s

Drive Units

eng x 10 radian/sec.

Factory Default

0.0 r/s

Minimum Value

0.0 r/s

Maximum Value

200.0 r/s

This parameter establishes the breakpoint
radian frequency for the 10 Volt Input.

Pot In Filtr
[Pot In Filter]

Parameter Number

353

Parameter Type
Display Units

x.x r/s

Drive Units

eng. x 10 radian/sec

Factory Default

0.0 r/s

Minimum Value

0.0 r/s

Maximum Value

200.0 r/s

This parameter establishes the breakpoint
radian frequecy for the Pot Input.

mA In Filtr
[mA In Filter]

Parameter Number

354

Parameter Type
Display Units

x.x r/s

Drive Units

eng. x 10 radian/sec

Factory Default

0.0 r/s

Minimum Value

0.0 r/s

Maximum Value

200.0 r/s

This parameter establishes the breakpoint
for the mA Input.

Advertising