Chapter 6
Troubleshooting

6–6

Figure 6.2
Parameter 81 (Non–configurable Fault Status)

DC Bus Overvoltage Trip

Transistor Desaturation Trip

Groundfault Trip

Instantaneous Overcurrent Trip

Adapter Comm Loss detected by CP

Master/Slave Cable Loss

Master/Slave Enable Timeout

Not Used

Adapter Comm Loss detected by VP

Absolute Overspeed

Analog Power Supply Tolerance

Autocommission or Transistor Diagnostic Fail

Inverter Temperature Trip

Software Malfunction detected by VP (Task Overrun)

Software Malfunction detected by VP (Illegal Interrupt)

NOT USED

O O O O O O O O. O O O O O O O O

Bit#

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Figure 6.3
Parameter 80 (Powerup/Diagnostic Fault Status)

CP PROM Failure

CP Internal RAM Failure

CP External RAM Failure

CP Stack RAM Failure

CP/VP Dualport RAM Failure

NOT USED

NOT USED

NOT USED

VP Prom Failure

VP Internal RAM Failure

VP External RAM Failure

VP Stack RAM Failure

VP/CP Dualport RAM Failure

VP/AP Dualport RAM Failure

Base Drive EE Failure

NOT USED

O O O O O O O O. O O O O O O O O

Bit#

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

This word parameter indicates fault conditions in the Drive that CANNOT be configured as warnings. When a bit is set
to “1”, the corresponding condition in the Drive is true, otherwise the condition is false. Bit 0–3 are detected by hardware
and 4–15 are detected by software.

This word parameter indicates a fault condition which has been detected during power up or reset of the drive. Where
the bit is set to “1”, the corresponding condition in the Drive is true, otherwise the condition is false.