Rockwell Automation 1336T FORCE Series B User Manual

Page 117

Advertising
background image

Chapter 4
Startup

4–26

In

Figure

4.10 Analog Output 1 is used as an example to detail the scaling

and offset parameters. At Analog Output 1 a meter with a range of 0-10 V
DC has been connected. Parameter 370 has been linked to Parameter 146
(Velocity Feedback). In order for the meter to indicate speed in both
directions, the scale and offset parameters must be adjusted as shown in

Figure

4.10. Working in the opposite direction as the analog inputs, apply the

scale factor first. The drive sends a

±

4096 digital value to indicate

±

100%

velocity feedback for a total digital range of 8192. The meter, having an
analog range of 0-10V

DC, requires a digital range of 2048. This is

accomplished by applying a scale factor of 0.25 (8192

×

0.25 = 2048).

In order to have the 0-10V

DC meter indicate

±

100% feedback, an offset

must be applied. Offset parameters for analog outputs will again add the
corresponding digital value to the range. In this case, an offset of 5 volts adds
a digital value of 1024 to the range. This will allow full range deflection on
the 0 to 10 volt meter, with 5 volts indicating zero speed.

Figure 4.10.
Analog Output 1 +/– 100% Speed Indication

–100%

B. SPD.

0 SPD.

+100%

B. SPD

5V

0V

10V

+4096 (+100% SPEED)

0

–4096 (–100% SPEED)

+1024

0

–1024

+2048
+1024

0

+10V = + 100% BASE SPEED

+5V = 0 SPEED

SCALE

PAR 372

X 0.25

OFFSET
PAR 371

5V = 1024

D

A

SCALED BY 0.25

0V = –100%

OFFSET BY 5V, ADDING 1024

DIGITAL VALUE

METER VOLTAGE

% BASE SPEED

– 4096

– 1024

+ 1024

0

0 VOLTS

– 100%

0

0

+ 1024

0

5 VOLTS

0%

4096

+ 1024
+ 1024

2048

10 VOLTS

+ 100%

(

±

2048 =

±

10V)

PAR 146

PAR 370

VELOCITY

FEEDBACK

ANALOG OUT 1

DIGITAL RANGE

FROM DRIVE