Chapter 5
Programming Parameters

5–80

Analog Output 1 Scale
[An Out 1 Scale]

Parameter Number

372

Parameter Type

Sink

Display Units

+/– x.xxx

Drive Units

32767 = 1

Factory Default

+0.500

Minimum Value

–1.000

Maximum Value

+1.000

This parameter determines the scale factor
or gain for Analog Output 1. A +/– 32767
digital value is converted by the scale fac-
tor which allows an effective digital range
of +/– 2048 which is then offset to provide
a +/– 10 volt range.

Analog Output 2
[Analog Out 2]

Parameter Number

373

Parameter Type

Sink

Display Units

+/– x

Drive Units

None

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

This parameter converts a +/– 32767
digital value to a +/– 10 volt output.

Analog Output 2 Offset
[An Out 2 Offset]

Parameter Number

374

Parameter Type

Sink

Display Units

+/– x.xxx volt

Drive Units

205 = 1 volt

Factory Default

+0.000

Minimum Value

–20.000

Maximum Value

+20.000

This parameter determines the offset ap-
plied to the raw analog output 2. The offset
is applied after the scale factor.

Analog Output 2 Scale
[An Out 2 Scale]

Parameter Number

375

Parameter Type

Sink

Display Units

+/– x.xxx

Drive Units

32767 = 1

Factory Default

+0.500

Minimum Value

–1.000

Maximum Value

+1.000

This parameter determines the scale factor
or gain for Analog Output 2. A +/– 32767
digital value is converted by the scale fac-
tor which allows abn effective digital range
of +/– 2048 which is then offset to provide
a +/– 10 volt range.

Milli Amp Output
[mA Output]

Parameter Number

376

Parameter Type

Sink

Display Units

x

Drive Units

None

Factory Default

0

Minimum Value

0

Maximum Value

+32767

This parameter converts a +/– 32767
digital value to a 4–20 mA output.

Milli Amp Output Offset
[mA Output Offset]

Parameter Number

377

Parameter Type

Sink

Display Units

+/– x.xxx mA

Drive Units

128 = 1mA

Factory Default

0.000 mA

Minimum Value

–32.000 mA

Maximum Value

+32.000 mA

This parameter determines the offset ap-
plied to the raw milli amp output. The off-
set is applied after the scale factor.