Chapter 5
Programming Parameters

5–81

Milli Amp Output Scale
[mA Output Scale]

Parameter Number

378

Parameter Type

Sink

Display Units

+/– x.xxx

Drive Units

32767 = 1

Factory Default

+0.500

Minimum Value

–1.000

Maximum Value

1.000

This parameter determines the scale factor
or gain for milli amp output. A +/– 32767
digital value is converted by the scale fac-
tor which allows an effective digital range
of +/– 2048 which is then offset to provide
a +/– 20 mA range.

SCANport Analog Output
[SP Analog Out]

Parameter Number

379

Parameter Type

Sink

Display Units

+/–x

Drive Units

None

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

This parameter displays the analog value
that is sent to all SCANports

Programmable Output Select
[Output Select]

Parameter Number

384

Parameter Type

Sink,

Display Units

x

Drive Units

None

Factory Default

8

Minimum Value

0

Maximum Value

63

This parameter selects the function of
TB7–1 Output. The NOT column in the
following table indicates the value for the
inverse condition. For example: Entering
a value of 0 will result in a Run Ready
condition, while a value of 32
results in a NOT Run Ready condition.

NOT EN
32

0

RUN READY

33

1

RUNNING

34

2

COMMAND DIRECTION

35

3

ROTATING DIRECTION

36

4

ACCELERATING

37

5

DECELERATING

38

6

WARNING

39

7

FAULTED

40

8

AT SET SPEED

41

9

LOCAL A

42

10 LOCAL B

43

11 LOCAL C

44

12 AT ZERO SPEED

45

13 REF A

46

14 REF B

47

15 REF C

NOT EN
48

16 FLUX READY

49

17 FLUX UP

50

18 DIAGNOSTIC COMPLETED

51

19 DIAGNOSTIC ABORTED

52

20 BUS RIDETHRU

53

21 JOGGING

54

22 AUTOTUNE STAT A

55

23 AUTOTUNE STAT B

56

24 AT LIMIT

57

25 NOT USED

58

26 AT SETPOINT 1

59

27 AT SETPOINT 2

60

28 OVER SETPOINT 1

61

29 OVER SETPOINT 2

62

30 OVER SETPOINT 3

63

31 OVER SETPOINT 4

Set P66 to the type of Set Point desired,
Current or Speed.
Then set the appropriate parameter (P60 –
P65) to monitor your desired SetPoint.