Chapter 5
Programming Parameters

5–65

Stator Frequency
[Freq Command]

Parameter Number

266

Parameter Type

Source

Display Units

x .xxx Hz

Drive Units

128 @ 1Hz

Factory Default

0 .000 Hz

Minimum Value

–255.992 Hz

Maximum Value

+255.922 Hz

Displays the actual value of motor stator
frequency. Units are in Hz times 128 (128
@ 1 Hz)

Parameter Number

268

Parameter Type

Source

Display Units

x Vlt

Drive Units

None

Factory Default

0 volts

Minimum Value

0 volts

Maximum Value

1,000 volts

DC Bus Voltage
[DC Bus Voltage]

Inverter Temperature Feedback
[Inv Temp Fdbk]

Parameter Number

270

Parameter Type

Source

Display Units

+/– x deg

Drive Units

None

Factory Default

0 deg

Minimum Value

– 50 deg

Maximum Value

+255 deg

This is the actual Bus Voltage as read by
the software from an analog input port.
Units are in volts.

Inverter temperature determined by NTC
device on heatsink power structure.
Can be configured to generate either a
warning or fault when heatsink reaches 80
degrees C.

Filtered Velocity Feedback
[Filt Vel Fdbk]

Parameter Number

269

Parameter Type

Source

Display Units

x.x rpm

Drive Units

4096 = base motor speed

Factory Default

0.0 rpm

Minimum Value

– 8 x Base Speed

Maximum Value

+8 x Base Speed

This parameter contains a filtered version
of velocity feedback. The value contained
in this parameter is not meant to be used
for control, only for display and monitoring
purposes.

Limited Motor Flux
[Lim Motor Flux]

Parameter Number

271

Parameter Type

Source

Display Units

x.x%

Drive Units

4096 = 100% flux

Factory Default

100%

Minimum Value

12.5%

Maximum Value

100%

This parameter displays the level of motor
field flux calculated by the current proces-
sor and limited by the Min Flux Level
parameter (Param 174).

Parameter Number

267

Parameter Type

Source

Display Units

+/– x.x%

Drive Units

4096 = 100.0 %

Factory Default

0.0

Minimum Value

–800.0%

Maximum Value

+800.0%

Calculated Torque
[Calc Torque]

This parameter will display the calculated
value of motor torque as determined by the
Velocity Processor. The actual value of
motor torque will be within 5% of this value.
Scaling is 4096 at rated motor torque. This
data is updated on a 2 millisecond basis.

Testpoint Selection #1
[Torq TP Sel 1]

Parameter Number

273

Parameter Type

Sink

Display Units

x

Drive Units

None

Factory Default

0

Minimum Value

0

Maximum Value

100

This parameter selects a torque block test
point. The value of that test point can be
read from Torq TP Data 1 (Parm 274).