Chapter 2
Installation/Wiring
2–39
Figure 2.26.
Option L4/L4E Wiring
19
20
21
22
23
24
25
26
27
28
29
30
31
32
A
A
ENC
RET
ENC
12V
33
34
35
36
Typical of Each Input
Typical
L4, L4E Options
Isolated
+5V
Isolated
Ground
0.1
µ
f
0.1
µ
f
0.1
µ
f
10.7k
470
470
12V
681
100
90.9
5V
JP4
IGND
10.7k
Contacts shown are general, refer to Figure 2.24 for
Input Mode selection and recommended contact types.
TB3
NOT
USED
Option L4/L4E – Contact Closure Interface Board Requirements
Circuits used with Option L4/L4E must be capable of operating with low =
true logic. Reed type input devices are recommended.
In the low state, external circuits must be capable of a sinking current of
approximately 10mA to pull the terminal voltage low to 3.0V DC or less.
In the high state, external circuits must allow the terminal voltage to rise to
a voltage of 4.0–5.0V DC.
The L4/L4E option is compatible with the following Allen–Bradley PLC
modules:
•
1771–OYL
•
1771–OZL