Chapter 5
Programming Parameters

5–82

I/O Stop Select 1
[Stop Select 1]

Parameter Number

387

Parameter Type

Sink

Display Units

x

Drive Units

None

Factory Default

0

Minimum Value

0

Maximum Value

3

This parameter selects the stopping mode
for a valid stop command.
3 = Param 59 Bits 4 or 5
2 = Current limit stop
1 = Ramp Stop
0 = Coast Stop

Input Status
[Input Status]

Parameter Number

386

Parameter Type

Source

Display Units

Bit

Drive Units

None

Factory Default

0000 0000

Minimum Value

0000 0000

Maximum Value

1111 1111

Enums:

This parameter displays the on/off status of
inputs 1-8 at TB3.
1 = ON
0 = Off

Bit

Condition

0
1
2

Input 1
Input 2
Input 3

Bit

Condition

3
4
5

Input 4
Input 5
Input 6

Bit

Condition

6
7

Input 7
Input 8

Input Mode
[Input Mode]

Parameter Number

385

Parameter Type

Sink

Display Units

x

Drive Units

None

Factory Default

1

Minimum Value

1

Maximum Value

30

Enums:

This parameter selects the functions of the
inputs 1-9 at TB3.

Mode
1
2
3
4
5, 27
6
7
8
9, 28
10, 29
11
12
13
14
15, 30
16
17
18
19
20
21
22
23
24
25
26

Input 1
Status
Start
Start
Start
Start
Start
Start
Start
Start
Start
Start
Run Fwd
Run Fwd
Run Fwd
Run Fwd
Run Fwd
Start
Start
Start
Start
Start
Start
Run Fwd
Run Fwd
Run Fwd
Run Fwd

Input 2
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop

Input 3
Status
Rev/Fwd
Rev/Fwd
Rev/Fwd
Rev/Fwd
Rev/Fwd
Rev
Rev
Pot Up
Rev
1st Acc
Run Rev
Run Rev
Run Rev
Run Rev
Run Rev
Rev/Fwd
Rev/Fwd
Spd/Trq3
Spd/Trq3
Rev
Spd/Trq3
Run Rev
Run Rev
Run Rev
Run Rev

Input 4
Status
Jog
Stop Type
1/2 Acc
Pot Up
Jog
Fwd
Fwd
Pot On
Fwd
2nd Acc
Loc/Rem
Stop Type
1/2 Acc
Pot up
Loc/Rem
Proc Trim
Flux En
Spd/Trq2
Spd/Trq2
Fwd
Spd/Trq2
Proc Trim
Flux En
Proc Trim
Jog

Input 5
Status
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault
Ext Fault

Input 6
Status
Spd 3
Spd 3
1/2 Dec
Pot Dn
Loc/Rem
Jog
Spd 3
Spd 3
Pot Up
1st Dec
Spd 3
Spd 3
1/2 Dec
Pot Dn
Stop Type
Ramp
Reset
Spd/Trq1
Spd/Trq2
Ramp
Spd/Trq1
Reset
Reset
Ramp
Spd 3

Input 7
Status
Spd 2
Spd 2
Spd 2
Spd 2
Spd 2
Spd 2
Spd 2
Spd 2
Pot Dn
2nd Dec
Spd 2
Spd 2
Spd 2
Spd 2
Spd 2
Spd 2
Spd 2
Proc Trim
Flux En
Reset
Spd 2
Spd 2
Spd 2
Spd 2
Spd 2

Input 8
Status
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1
Spd 1

Advertising