Rockwell Automation 1336T FORCE Series B User Manual

Page 211

Advertising
background image

Chapter 5
Programming Parameters

5–85

Fault Status
[SA Fault Status]

Parameter Number

407

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1110 0001 0111 1111

Enums:

This parameter displays the fault status of
the SCANport device.
1 = Fault
0 = No Fault

Bit 0 – Not Used
Bit 1 – SCANport Device 1
Bit 2 – SCANport Device 2
Bit 3 – SCANport Device 3
Bit 4 – SCANport Device 4
Bit 5 – SCANport Device 5

Bit 6 – SCANport Device 6
Bit 7 – Not Used
Bit 8 – 4 – 20 mA Loss
Bit 9 – Not Used
Bit 10 – Not Used
Bit 11 – Not Used

Bit 12 – Not Used
Bit 13 – Illegal Drive Type (Not Configurable)
Bit 14 – Diff Drive Type (Not Configurable)
Bit 15 – SCANport error (Not configurable)

Warning Status
[SA Warn Status]

This parameter displays the warning status
of the SCANport device timeouts.
1 = Warning
0 = No Warning

Bit 0 – Not Used
Bit 1 – SCANport Device 1
Bit 2 – SCANport Device 2
Bit 3 – SCANport Device 3

Bit 4 – SCANport Device 4
Bit 5 – SCANport Device 5
Bit 6 – SCANport Device 6

Parameter Number

408

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

0000 0001 0111 1111

Enums:

Bit 8 – 4–20 mA Loss
Bit 9–15 – Not Used

Fault Select
[SA Fault Select]

Parameter Number

405

Parameter Type

Sink

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0111 1111

Minimum Value

0000 0000 0000 0000

Maximum Value

0000 0001 0111 1111

Enums:

This parameter chooses whether a SCAN-
port device causes a drive fault, a warning
based on ‘SA Warn Sel’ (P406) or does
nothing.
1 = Fault
0 = Warning/Nothing

Bit 5 – SCANport Device 5
Bit 6 – SCANport Device 6
Bit 7 – Not Used
Bit 8 – 4–20 mA Loss
Bit 9–15 – Not Used

Warning Select
[SA Warn Select]

Parameter Number

406

Parameter Type

Sink

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0111 1111

Minimum Value

0000 0000 0000 0000

Maximum Value

0000 0001 0111 1111

Enums:

This parameter selects whether a SCAN-
port device timeout causes a warning or
does nothing.
1 = Warning
0 = Does Nothing

Bit 0 – Not Used
Bit 1 – SCANport Device 1
Bit 2 – SCANport Device 2
Bit 3 – SCANport Device 3
Bit 4 – SCANport Device 4

Bit 5 – SCANport Device 5
Bit 6 – SCANport Device 6
Bit 7 – Not Used
Bit 8 – 4–20 mA Loss
Bit 9–15 – Not Used

Bit 0 – Not Used
Bit 1 – SCANport Device 1
Bit 2 – SCANport Device 2
Bit 3 – SCANport Device 3
Bit 4 – SCANport Device 4

Advertising