Chapter 2
Installation/Wiring

2–21

Power Wiring

On 1 to 30 HP drives, input and output power connections are performed
through a 10 position terminal block, TB1 located on the Gate Driver
Board. On drives larger than 30 HP, input and output power connections
are made at seperate terminal strips located at the bottom of the drive. The
drive connections are illustrated in Figure 2.10. The C thru G
configurations of TB1 are stud terminations and require the use of lug type
connectors to terminate the field installed conductors. Cat. No.
1336–LUG–XXXX Lug Kits are available for use with these
configurations of TB1. The wire size used is determined by selecting the
proper lug kit based on the Cat. No. of the drive. Refer to Table 2.C to
determine the correct lug kit for your application.

Figure 2.10.
Terminal Block TB1

PE

PE

R

(L1)

S

(L2)

T

(L3)

U

(T1)

V

(T2)

W

(T3)

DC

+

DC

Required

1

Input Fusing

AC Input Line

To Motor

200–240V, 7.5–11 kW (10–15 HP) Terminal Designations

380–480V, 15–22 kW (20–30 HP) Terminal Designations

500–600V, 15 kW (20 HP) Terminal Designations

Dynamic Brake

To Motor

1

Required Branch

Circuit Disconnect

B1

Frame

B2

Frame

PE

PE

R

(L1)

S

(L2)

T

(L3)

U

(T1)

V

(T2)

W

(T3)

DC

+

DC

AC Input Line

To Motor

To Motor

200–240V, 0.75–5.5 kW (1–7.5 HP) Terminal Designations

380–480/500–600V, 0.75–11 kW (1–15 HP) Terminal Designations

Dynamic Brake

Required

1

Input Fusing

1

Required Branch

Circuit Disconnect