PLC Communication Adapter Board

Control and Signal Wiring – When installing and wiring the PLC
Communication Adapter Board, you need to deal with the following issues:

Control and Signal Wiring

Jumper Settings for I/O Circuits

If your 1336 FORCE Drive is equipped with a PLC Comm Adapter Board,
terminal blocks TB20 & TB21 located at the bottom center of the PLC
Comm Board (Figure 2.29) are used for control and signal wiring (Drive
Permissives). Connector TB21 provides the interface for Analog Input and
Output reference signals as detailed in Figure 2.30.

Figure 2.29.
PLC Comm Board Connections

AP
Status

LANGUAGE
MODULE

DP Status

1

CH A High

J5


TP1

Port 1

DOMINO
ADAPTER

RIO
Channel A

Communication Modes

U2

U3

U4

U5

10

TB20

TB21

1

19

CH A Low

CH B Low

CH B High

D3

D6

D8

D10

D12

D13

D14

D15

CH A
Status

CH B
Status

J7

D1

D2

Port 2


TP2


TP3


TP4


TP5

ADC Inputs

DAC Inputs

J1

Main Control
Interface

Drive Permissives

J4

J3

120 V

RIO
Channel B

BRAM
Enable

Ref

D4

D5

Fault Out

Ext Fault

D7

Norm Stop

Motor Thermo

D9

Drive Enable

D11

24 V

120 V

24 V

120 V

24 V

120 V

24 V

J11

J10

J9

J8

Drive En

M Therm

N Stop

X Flt

EN

DIS

Fuse
1 – 4

TP24

+10V Ref

TP25

–10V Ref

ON

ON

ON

ON

DGND +5V

+15V

–15V

AGND

NOTE: For more information on the PLC Communication Board
including LEDs and Jumpers, refer to the PLC Communication User
Manual 1336 FORCE 5.13.

CHANNEL A

SHIELD

CHANNEL B

2

1

SHIELD

2

1

The maximum and minimum wire size accepted by TB20, TB21, Channel
A and Channel B is 3.3 and 0.06 mm

2

(12 and 30 AWG). Maximum

torque for these terminal blocks is 0.79 N–m (7 lb. – in.). Only copper
wire may be used.