Chapter 6
Troubleshooting

6–19

Figure 6.8
Parameter 85 (VP Configurable Warning Status (bits))

Feedback Loss

Inverter Overtemp Pending

Motor Overtemperature Tripped

Motor Overload Pending – IIT

Motor Overload Trip – IIT

Motor Stalled

External Fault

RMS Fault

NOT USED

Parameter Limit

Math Limit

Dynamic Brake Resistor Overtemperature

AC Motor Contactor Failure

Inverter Overload Pending (IT)

Drive–to–Drive communication fault

Inverter Overload Foldback (IT)

O O O O O O O O. O O O O O O O O

Bit#

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

This word parameter indicates conditions detected by the Velocity Processor (VP) that have been configured to report as
a Drive warning condition. Each configuration bit matches the bit definitions of Parameters 83, 88 and 89. When a bit is
set to “1”, the corresponding condition in the Drive is true, otherwise the condition is false.

Advertising