Rockwell Automation 1336T FORCE Series B User Manual

Page 186

Advertising
background image

Chapter 5
Programming Parameters

5–60

CP Operating Options
[CP Options]

Parameter Number

227

Parameter Type

Sink

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

0000 0000 0011 0000

For proper operation, bits 0 to 6 must be
left at zero.
If bit 7 = 0, this allows the motor to coast to
a stop after the flux test is completed.
If bit 7 = 1, this brings the motor to a con-
trolled stop after the flux test is completed.

Parameter Number

228

Parameter Type

Sink

Display Units

x.x HP

Drive Units

Display units x 10

Factory Default

30.0 HP

Minimum Value

1.0 HP

Maximum Value

HP

Base Motor Speed
[Base Motor Speed]

Motor Nameplate Horsepower
[Base Motor HP]

Parameter Number

229

Parameter Type

Sink

Display Units

x RPM

Drive Units

x

Factory Default

1,750 RPM

Minimum Value

1 RPM

Maximum Value

15,000 RPM

Motor Nameplate AMPS
[Base Motor Curr]

Parameter Number

230

Parameter Type

Sink

Display Units

x.x amps

Drive Units

Display units x 10

Factory Default

0.2 amps

Minimum Value

0.1 amps

Maximum Value

Based on parameter 220

Drive nameplate current rating of the
motor. Used for current reference scaling
and current processor feedback scaling.

User entered value of nameplate motor
horsepower. The drive uses this informa-
tion in the Dynamic Brake Resistor
temperature calculation.

User entered value of nameplate motor
speed in RPM. The drive uses this
information to convert motor velocity RPM
to/from drive per unit.

Motor Nameplate VOLTS
[Base Motor Volt]

Parameter Number

231

Parameter Type

Sink

Display Units

x Volt

Drive Units

None

Factory Default

460 volt

Minimum Value

75 volt

Maximum Value

575 volt

Motor Nameplate Frequency
[Base Motor Freq]

Parameter Number

232

Parameter Type

Sink

Display Units

x.x Hz

Drive Units

display units x 10

Factory Default

60 Hz

Minimum Value

1 Hz

Maximum Value

250 Hz

Drive nameplate voltage rating of the
motor.

Total number of motor poles in motor.

Motor Nameplate Poles
[Motor Poles]

Parameter Number

233

Parameter Type

Sink

Display Units

x poles

Drive Units

None

Factory Default

4 poles

Minimum Value

2 poles

Maximum Value

40 poles

Motor Inertia
[Motor Inertia]

Parameter Number

234

Parameter Type

Sink

Display Units

x.xx Sec

Drive Units

Display units x 100

Factory Default

0.60 Sec

Minimum Value

0.01 Sec

Maximum Value

655 Sec

Time taken to accelerate
an uncoupled motor from zero to base
speed at rated torque.

Drive nameplate frequency rating of the
motor.

Advertising