Signal ground ú te, Safety ground ú pe, Rfi filter – Rockwell Automation 1336T FORCE Series B User Manual

Page 36

Advertising
background image

Chapter 2
Installation/Wiring

2–16

Signal Ground – TE

The TE terminal block is used for all control signal shields internal to the
drive. It must be connected to an earth ground by a separate continuous
lead.

Any PLC I/O communication link must be run in grounded steel conduit.
The conduit should be bonded to ground at both ends. Ground the cable
shield at the drive end only.

The maximum and minimum wire size accepted by this block is 2.1 and
0.30 mm2 (14 and 22 AWG). Maximum torque is 1.36 N–m (12 lb.–in.).
Use Copper wire Only.

Safety Ground – PE

This is the safety ground required by code. The ground bus can be
connected to adjacent building steel (girder, joist) or a floor ground loop,
provided grounding points comply with NEC regulations.

RFI Filter

Important: Using an optional RFI filter may result in relatively high ground
leakage currents. Surge suppression devices are also incorporated in the
filter to clamp line surges to a limited voltage above ground potential.
Therefore, the filter must be permanently installed and solidly grounded.
Grounding must not rely on flexible cables and should not include any
form of plug or socket that would permit inadvertent disconnection. The
integrity of this connection should be periodically checked.

Figure 2.8.
Recommended 1336 FORCE Grounding

JOG

ESC

SEL

R (L1)

S (L2)

PE

Ground Rod

T (L3)

PE

U (T1)

Shield

RIO/DH+

Shield

Common

Mode

Core

Common

Mode Core

Conduit/4–Wire Cable

To Computer

TE Ground

+ Common

Mode

Chokes*

*These are options that can

be installed as needed

Ground per

Local Codes

Motor Frame

Motor

Terminator

PE

V (T2)

W (T3)

PE/Gnd.

+DC

DC