Option L6/L6E – 115V AC Interface Board Requirements

Circuits used with Option L6/L6E must be capable of operating with high
= true logic. In the low state, circuits must generate a voltage of no more
than 30V AC. Leakage current must be less than 10 mA into a 6.5k ohm
load. In the high state, circuits must generate a voltage of 90–115V AC
+/–10% and source a current of approximately 20 mA for each input.
The L6/L6E option is compatible with these Allen–Bradley PLC modules:

1771–OW

1771–OA

1771–OWN

1771–OAD (contact factory for recommended series/

rev. level.)