Rockwell Automation 1336T FORCE Series B User Manual

Page 203

Advertising
background image

Chapter 5
Programming Parameters

5–77

10 Volt Input
[10 Volt Input]

Parameter Number

355

Parameter Type

Source

Display Units

+/– x

Drive Units

None

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

This parameter displays the converted
analog value of the +/– 10 volt input.

10 Volt Offset
[10 Volt Offset]

Parameter Number

356

Parameter Type

Sink

Display Units

+/– x.xx volt

Drive Units

205 = 1 volt

Factory Default

+0.00 volt

Minimum Value

–20.00 volt

Maximum Value

+20.00 volt

This parameter determines the offset ap-
plied to the raw analog value of the +/– 10
volt input before the scale factor is applied.
This allows the user to shift the range of
the analog input.

10 Volt Scale
[10 Volt Scale]

Parameter Number

357

Parameter Type

Sink

Display Units

+/– x.xxx

Drive Units

2048 = 1

Factory Default

+2.000

Minimum Value

–16.000

Maximum Value

+16.000

This parameter determines the scale factor
or gain for the +/– 10 volt input. The +/– 10
volt input is converted to +/– 2048 and
then the scale is applied which allows an
effective digital range of +/– 32767.

Pot Input
[Pot Input]

Parameter Number

358

Parameter Type

Source

Display Units

+/– x

Drive Units

None

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

This parameter displays the converted
analog value of the pot input.

Pot Offset
[Pot Offset]

Parameter Number

359

Parameter Type

Sink

Display Units

+/– x.xx volts

Drive Units

205 = 1 volt

Factory Default

+0.000 volt

Minimum Value

–20.000 volt

Maximum Value

+20.000 volt

This parameter determines the offset
applied to the raw analog value of the pot
input before the scale factor is applied.
This allows the user to shift the range of
the of the analog input.

Pot Scale
[Pot Scale]

Parameter Number

360

Parameter Type

Sink

Display Units

+/– x.xxx

Drive Units

2048 = 1

Factory Default

+1.000

Minimum Value

–16.000

Maximum Value

+16.000

This parameter determines the scale factor
or gain for the pot input. The pot input is
converted to a +/– 2048 and then the scale
is applied allowing an effective digital range
of +/– 32767

Milli Amp Input
[mA Input]

Parameter Number

361

Parameter Type

Source

Display Units

x

Drive Units

None

Factory Default

+0

Minimum Value

0

Maximum Value

+32767

This parameter displays the converted
analog value of the milli amp input.

Advertising