Standard adapter board, 18 awg), twisted pair, shielded – Rockwell Automation 1336T FORCE Series B User Manual

Page 48

Advertising
background image

Chapter 2
Installation/Wiring

2–28

Standard Adapter Board

When installing and wiring the Standard Adapter board, you need to deal
with the following issues:

Control and Signal Wiring

Interface Board Installation and Removal

Control & Signal Wiring – If your 1336 FORCE Drive is equipped with
a Standard Adapter Board, terminal blocks TB5, TB6 and TB7 located at
the bottom center of the board (Figure 2.15) are used for control and signal
wiring (Drive Permissives). The Standard Adapter Board is connected to
the Main Control Board through J1, the Main Control Interface.

The maximum and minimum wire size accepted by TB5, TB6 and TB7 is
3.3 and 0.06 mm

2

(12 and 30 AWG). Maximum torque for these terminal

blocks is 0.79 N–m (7 lb. – in.). Recommended control signal wire is:

Belden 8760 or equiv. – 0.750 mm

2

(18 AWG), Twisted Pair, Shielded

Belden 8770 or equiv. – 0.750 mm

2

(18 AWG), 3 – Conductor, Shielded

Belden 9460 or equiv. – 0.750 mm

2

(18 AWG), Twisted Pair, Shielded

Figure 2.15.
Standard Adapter Board Connections

LANGUAGE
MODULE

1

J11


TP1

Port 1

TB5

J9

D1

TE

Port 2


TP3

J1

Main Control
Interface

J5

BRAM

АААААА

АААААА


TP2


TP6


TP5

+5V

DGND

+15V

AGND

–15V

EN

DIS

D2

1

L OPTION BOARD

TB6

TB7

TP7

TP8

12V ISO

ISO COM

Jumper

J13

J13

3

1

+5V DC

1 to 2

+12V DC

2 to 3

Purpose

Jumper

J5

Position

1 to 2
2 to 3

Purpose

BRAM Write Enable
BRAM Write Disabled

14

12

1

8

Status

LED

STATE

DESCRIPTION

D1 (Green)

OFF

Flashing

Solid ON

D2 On or No Power

Adapter Warning Fault

Adapter OK

D2 (RED)

OFF

Flashing

Solid ON

D1 On or No Power

Adapter Soft Fault

Adapter Hard Fault

TE

1

20

J10

J12

20

1

Refer to Fault Codes in Table 6.B