Rockwell Automation 1336T FORCE Series B User Manual

Page 166

Advertising
background image

Chapter 5
Programming Parameters

5–40

Over Setpoint 3
[Over Setpoint 3]

Parameter Number

64

Parameter Type

Sink

Display Units

+/– x.x%

Drive Units

4096 = 100.0% setpoint

Factory Default

+0.0 %

Minimum Value

–800.0%

Maximum Value

+800.0%

Over Setpoint 4
[Over Setpoint 4]

Parameter Number

65

Parameter Type

Sink

Display Units

+/– x.x %

Drive Units

4096 = 100% setpoint

Factory Default

+0.0 %

Minimum Value

–800%

Maximum Value

+800%

This parameter is used to specify the set-
point threshold for the Over Setpoint 3 bit
in Logic Status Hi.

This parameter is used to specify the set-
point threshold for the Over Setpoint 4 bit
in Logic Status Hi.

Current Setpoint Tolerance
[Cur Setpoint Tol]

Parameter Number

68

Parameter Type

Sink

Display Units

x.x%

Drive Units

4096 = 100.0% Iq

Factory Default

2.0%

Minimum Value

0.0%

Maximum Value

20.0%

This parameter establishes a hysteresis
band around the Setpoints. It will be used
to determine when to update the Setpoint
Bits in Logic Status Hi (P57), when config-
ured for commanded current option.

Speed Setpoint Tolerance
[Speed Setpnt Tol]

Parameter Number

67

Parameter Type

Sink

Display Units

x.x rpm

Drive Units

4096 = base speed

Factory Default

base sp / 100

Minimum Value

0.0 rpm

Maximum Value

base speed /10

This parameter establishes a hysteresis
band around the At Setpoints. It will be
used to determine when to update the Set-
point Bits in the Logic Status Hi (P57),
when configured for actual speed option.

Zero Speed Tolerance
[Zero Speed Tol]

Parameter Number

69

Parameter Type

Sink

Display Units

+/– x%

Drive Units

4096 = base speed

Factory Default

base speed / 100

Minimum Value

0.0 rpm

Maximum Value

8 x base speed

This parameter establishes a band around
zero speed that will be used to determine
when to update the At Zero Speed bit in
the Logic Status Low (P56).

Setpoint Select
[Setpoint Select]

Parameter Number

66

Parameter Type

Sink

Display Units

Bits

Drive Units

bit clear = speed, set = current

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

0000 0000 1111 1111

Enums:

This parameter makes a selection between
actual speed or internal Iq current refer-
ence for the At/Over Setpoint parameters.
Each Setpoint Status bit can be set for ei-
ther option ( 0 = Actual Speed; 1 = Iq Ref-
erence).

Bit 0 = At Setpoint 1
Bit 1 = At Setpoint 2
Bit 2 = Over Setpoint 1
Bit 3 = Over Setpoint 2

Bit 4 = Over Setpoint 3
Bit 5 = Over Setpoint 4

Logic Testpoint Data
[Logic Tstpt Data]

This parameter contains the logic control
testpoint data that has been selected by
the Logic Tstpt Sel parameter, P71.

Parameter Number

70

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111