Appendix a, A–13, Of drive rated amps – Rockwell Automation 1336T FORCE Series B User Manual

Page 261: Carrier frequency in khz, Of drive rated amps altitude, Figure 31 required only for the following drives

Advertising
background image

Appendix A

A–13

Standard Rating for Enclosed Drive in 40

°

C Ambient & Open Drive in 50

°

C Ambient

Derating Factor for Enclosed Drive in Ambient between 41

°

C & 50

°

C.

Figure 28
1336T–C600

70%

85%

75%

80%

90%

95%

100%

% of Drive

Rated Amps

65%

Carrier Frequency in kHz

60%

55%

1

4

3

2

Figure 29
1336T–C650

70%

85%

75%

80%

90%

95%

100%

% of Drive

Rated Amps

65%

60%

55%

Carrier Frequency in kHz

50%

1

4

3

2

% of Drive

Rated Amps

Altitude

m
(ft)

100%

80%

90%

0

4,000

(13,200)

3,000

(9,900)

2,000

(6,600)

1,000

(3,300)

Figure 30
All Drive Ratings

% of Drive

Rated Amps

Input Voltage

100%

80%

90%

240, 480 or 600V Nominal

+6%

+4%

+2%

+10%

+8%

Figure 31
Required Only for the following drives:

1336T–A/B/C–025 18.5 kW (25 HP) at 8 kHz
1336T–A/B/C 22 kW (30 HP) at 6–8 kHz
1336T–A/B/C 45 kW (60 HP) at 6 kHz