Chapter 2
Installation/Wiring

2–30

Analog Inputs – There are (2) analog inputs to the Standard Adapter
Board (Figure 2.18) that have a range of

±

10V, (1) 4–20 mA analog input

and (1) pulse source input with a digital resolution of 12 bits. These inputs
are differential inputs with noise rejection filtering.

Each input has a gain and offset adjustment. The A/D converter is a 12 bit
device where an input value of +10V will result in a digital value of 2048.
Likewise, an input value of –10V will result in a digital output value of
–2048.

NOTE: Analog input parameters must be linked to a velocity reference
parameter as well as a scaling and offset parameter for an analog input to
function.

NOTE: Refer to Chapter 4, Startup, for Analog I/O configuration
information.

Figure 2.18
Analog Input Connections

Typical Connections for Unidirectional Operation

Typical Connections for Bidirectional Operation

COM (POWER SUPPLY COMMON)

IN + (ANALOG IN)

+ 10V DC (POWER SUPPLY)

IN (ANALOG IN)

REFERENCE POT
2.5 k

MINIMUM

TB5

1

– 10V DC (POWER SUPPLY) 3

ADC

REVERSE

FORWARD

R

Reverse

Reverse

Relay

Forward

6

0 to
+/–10V

7

8

2

COM (POWER SUPPLY COMMON)

IN + (ANALOG IN)

+ 10V DC (POWER SUPPLY)

IN (ANALOG IN)

2

6

REFERENCE POT
2.5 k

MINIMUM

TB5

Connect to
Either 1 or 3
(ONLY ONE)

1

– 10V DC (POWER SUPPLY) 3

ADC

7

8

0 to
+/–10V