Chapter 2
Installation/Wiring

2–29

Interface Board Installation and Removal
IMPORTANT: If the L Option Board is being installed, Standard Adapter
Board jumpers at pins 3 & 4 and 17 & 18 of J10 must be removed and the
proper Input Mode selected (Figure 2.16). If the L Option board is
removed, these jumpers must be reinstalled and the Input Mode parameter
must be programmed to “1”.

Figure 2.16.
Interface Board Jumper Locations

JOG

ESC

SEL

Figure 2.17.
Reference Signal Connections (Standard Adapter Board)

TB5

1

2

3

4

5

6

7

8

9

10 11 12

TB6

13 14

TB7

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

9

10 11 12

+10V

–10V

Com

+

SH

+

+

4 to 20ma

0 to

±

10V

SH

SH

+

Pulse

Source

0 to

±

10V

+

SH

+

0 to

±

10V

4 – 20 ma

SH

+

Analog

Outputs

Run

Fault

Relay

Alarm
Relay

TE

TE

Program

mable*

Run

Fault

Alarm

Terminal #

TB5

Signal

SH

Shield Ground

1,2,3

DC Power Supply

4,5,6,7

Input Impedance = 20K Ohms

10,11

Pulse Input for
Frequency Ref.:

+5V DC – Jumper xx Set to xx

+12V DC – Jumper xx Set to xx

Scale Factor (Pulse PPR) must be set

TB6

SH

1,2,4,5

Shield Ground

0 to +/– 10 V
DC Output:

Output Impedance = 100 Ohms

7,8

4 – 20 ma DC Output

Input Impedance = 130 Ohms

13,14

4 – 20ma Input:

Output Impedance = 100 Ohms

TB7

TE

4,5,6

Logic Earth Ground / Shield Ground

Fault Contact

Resistive Rating = 115VAC/30VDC, 5.0A
Inductive Rating = 115VAC/30VDC, 2.0A

7,8,9

Alarm Contact

Resistive Rating = 115VAC/30VDC, 5.0A
Inductive Rating = 115VAC/30VDC, 2.0A

Programmable

Supply

Note: This output is programmable through P384

If using a
potentiometer
reference* 2.5K

minimum

* External to Drive

DC Power Supply

+/– 10VDC, 50 mA per voltage

Output Impedance = 20 Ohms

User Supplied Analog Device

0 to +/– 10V DC Input:

Terminal Block