Defective. figure 34 on – Nortel Networks Circuit Card User Manual

Page 243

Advertising
background image

NT5D11 and NT5D14 Lineside T1 Interface cards

Page 243 of 906

Circuit Card

Description and Installation

Test 2, external loopback, assumes an external loopback is applied to the T1
link. Test data is generated and received by the lineside T1 card on all
timeslots. If test 1 passes but test 2 fails, it indicates that the T1 link is
defective between the lineside T1 card and the external loopback location. If
test 1 was not run and test 2 fails, the T1 link or the lineside T1 card could be
defective. To isolate the failure to the T1 link, tests 1 and 2 must be run in
tandem. Figure 35 demonstrates how an external loopback is applied to the
T1 link.

Test 3, network loopback, loops the received T1 data back toward the CPE
equipment. No test data is generated or received by the lineside T1 card. If
test 2 passes but test 3 fails, it indicates that the CPE device is defective. If
test 2 was not run and test 3 fails, the T1 link or the CPE device could be
defective. To isolate the failure to the CPE device, tests 2 and 3 must be run

Figure 34
MMI local loopback test

Figure 35
MMI external loopback test

T-1 link

Line side

T-1

interface

card

Customer

premise

equipment

(CPE)

Common

Equipment

System

External

network

T-1 link

553-AAA1120

T-1 link

Line side

T-1

interface

card

Customer

premise

equipment

(CPE)

Common

Equipment

System

External

network

T-1 link

553-AAA1121