Nortel Networks Circuit Card User Manual
Page 645

NT8D15 E&M Trunk card
Page 645 of 906
Circuit Card
Description and Installation
Incoming calls
The far-end initiates calls as follows:
•
The ground is placed on the E lead in E&M signaling.
•
Dial pulses are subsequently applied from the far-end as ground open on
the E lead.
•
If the far-end is equipped for sending, the system can operate in any
mode (immediate start, delay dial, or wink start), as assigned on a start
arrangement basis. See Table 197.
— In immediate start mode, there is no start signal from the called
office. The seizure signal (off hook supervisory state) from the
far-end should be at least 150 ms. At the end of the seizure signal,
the far-end can start pulsing after the standard delay (normally 70 ms
minimum).
— In delay dial mode, a 256–384 ms off hook/on hook signal is
returned to the far-end immediately after receipt of the seizure
signal. When the far-end detects the on hook signal (start signal), the
far-end can start pulsing after the standard delay (normally 70 ms
minimum).
— In wink start mode, within a 128–256 ms period after receipt of the
seizure signal from the far-end, the called office transmits a 250 ms,
wink start, off hook/on hook signal to the calling office.
E&M Type II signaling
shows E&M Type II signaling patterns for incoming
and outgoing calls. Figure 152 on
shows Type II signaling patterns
Table 197
Operation Mode
Operation mode
Start arrangement
Immediate start
IMM
Delay dial
DDL
Wink start
WNK