L3-04 stall prevention selection during decel – Yaskawa iQpump Programming Manual User Manual

Page 102

Advertising
background image

102

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

Figure 1.86

Figure 91 Time Chart for Stall Prevention During Acceleration

The L3-02 parameter is set as a percentage of the iQpump drive rated output current. If the motor capacity is small compared to the

Drive’s capacity, or if the motor stalls during acceleration, lower the set value of L3-02.

L3-04 Stall Prevention Selection During Decel

The stall prevention during deceleration function adjusts the deceleration time in order to prevent OV fault trips during deceleration. If

L3-04 = “0: Disabled,” stall prevention is disabled and if the load is large and the deceleration time short enough the iQpump drive may

fault and stop.

If L3-04 = “1: General Purpose,” then the standard stall prevention function is enabled. If, during deceleration, the DC Bus voltage

exceeds the stall prevention level (see

Table 27

), the iQpump drive will discontinue decelerating and maintain speed. Once the DC Bus

voltage has dropped below the stall prevention level, the deceleration will continue down to the Speed Command level. See

Figure 92

.

Table 27 Stall Prevention During Decel

If L3-01 = “2: Intelligent,” the intelligent stall prevention is enabled. The active deceleration time is ignored and the iQpump drive will

attempt to decelerate as quickly as possible without causing the DC Bus voltage to exceed the stall prevention level.

The following figure demonstrates acceleration when L3-04 = “1 General Purpose”.

Figure 1.87

Figure 92 Time Chart for Stall Prevention During Deceleration

Setting

Description

0

Disabled

1

General Purpose (

factory default)

2

Intelligent

Drive Voltage

Stall Prevention Level during Deceleration (V)

240 Vac

380

480 Vac

E1-01

≥ 400 Vac

760

E1-01 < 400 Vac

660

Output

Frequency

Output

Current

a - Set accel time
b - Accel time is extended

L3-02

t

a

b

t

a

b

TIME

t

a

380/660/760 Vdc

t

Output

Frequency

DC Bus
Voltage

b

a - Set decel time
b - Decel time is extended

TIME