Modbus data tables, Reference data – Yaskawa iQpump Programming Manual User Manual

Page 88

Advertising
background image

88

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

Modbus Data Tables

The data tables are shown below. The types of data are as follows: Reference data, monitor data and broadcast data.

Reference Data

The reference data table is shown below. Reference data can be read and written to.

Table 22 Reference Data

Register No.

Contents

0000H

Reserved

0001H

Sequence Control

Bit 0

Run Forward 1: Run 0: Stop

Bit 1

Run Reverse 1: Run 0: Stop

Bit 2

External fault1: Fault (EFO)

Bit 3

Fault reset1: Reset command

Bit 4

ComNet

Bit 5

ComCtrl

Bit 6

Multi-function digital input command 3

Bit 7

Multi-function digital input command 4

Bit 8

Multi-function digital input command 5

Bit 9

Multi-function digital input command 6

Bit A

Multi-function digital input command 7

Bits B to F

Not used

0002H

Frequency reference (Set units using parameter o1-03)

0003H to 0005H

Not used

0006H

PI Setpoint

0007H

Analog output 1 setting (-11 V = 726 to 11 V = 726)

→ 10 V = 660

0008H

Analog output 2 setting (-11 V = 726 to 11 V = 726)

→ 10 V = 660

0009H

Multi-function contact output setting

Bit 0

Digital output 1 (Terminal M1-M2) 1: ON 0: OFF

Bit 1

Digital output 2 (Terminal M3-M4) 1: ON 0: OFF

Bit 2

Not Used

Bits 3 to 5

Not used

Bit 6

Set fault contact (terminal MA-MC) output using bit 7. 1: ON 0: OFF

Bit 7

Fault contact (terminal MA-MC) 1: ON 0: OFF

Bits 8 to F

Not used

000AH to 000EH

Not used

000FH

Reference selection settings

Bit 0

Not used

Bit 1

Input PI setpoint 1: Enabled 0: Disabled

Bits 3 to B

Not used

C

Broadcast data terminal S5 input 1: Enabled 0: Disabled

D

Broadcast data terminal S6 input 1: Enabled 0: Disabled

E

Broadcast data terminal S7 input 1: Enabled 0: Disabled

F

Not used

Note: Write 0 to all unused bits. Also, do not write data to reserved registers.

Advertising