Yaskawa iQpump Programming Manual User Manual

Page 48

Advertising
background image

48

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

Function: 3-Wire Control (Setting: 0)

When one of the digital inputs is programmed for 3-Wire control, that input becomes a Forward/Reverse directional input. Whenever the

input is open, the iQpump drive will be set for forward rotation of the motor shaft. If the input it closed, then the motor shaft will rotate in

the reverse direction whenever a there is a Run input. The S1 and S2 digital inputs will function as a Run and Stop input respectively.

Figure 1.32

Figure 32 Terminal Configuration for 3-Wire Control

Figure 1.33

Figure 33 3-Wire Control Timing Diagram

Important: As long as the S1(Run Command) input is applied in for at least 50 ms the Run command will latch internally in the Drive.

Function: Local/Remote Selection (Setting: 1)

This function has been disabled. Please refer to settings “6D” and “6E”.

Function: Option/Inv Selection 1 (Setting: 2)

The Option/Inv Selection function allows the user to select the source for the Run and speed commands between either the Drive’s

terminals or an optional communication card. When a digital input is programmed for the Option/Inv Selection function (H1-0x = 2) that

input will function as follows:

Table 9 Digital Input Functions

To switch the command source between the option card and the terminals be sure to program the following parameters:

• Set b1-01 (Auto Setpoint Reference Selection) to 1 (Terminals).

• Set b1-02 (Run Command Selection) to 1 (Terminals).

• Set H1-0x (Input Terminal Function Selection) to 2.

Important: Switching between the different Reference and Run sources can only be done while the iQpump drive is stopped.

Option/Inv Selection Input Status

Run and Speed Command Source

CLOSED

From the control circuit and analog input terminals

OPEN

From the Communications Option Card

3-wire control

Stop switch
(NC contact)

Operation switch
(NO contact)

Run command
(run on momentary close)
Stop command
(stop on momentary open)

Sequence input common

SN

50 ms min.

Run command

Forward/reverse
command

Motor speed

Can be either ON or OFF

OFF

(stopped)

OFF (forward)

ON (reverse)

Stop

Forward

Reverse

Stop

Forward

Stop command

TIME

Advertising