YASKAWA TM.iQp.02 iQpump Drive Programming Manual

123

Figure 1.96

Figure 101

Note: When the Fixed Speed Auto is activated, the sleep and lead-lag functions are disabled. This configuration is only active

in Auto Mode.

The L4-01 parameter of the last drive controls the previous drive and activates the Auto Mode (when the frequency level drops below

L4-01).

iQ Pu m p

Run

S 1

Pressure Feedback

(H3-09 = B)

A 2 (4-20m A )

Pump Fault

(H1-01 = 24)

S 3 (H1-01)

Fault Reset

(H1-02 = 14)

S 4 (H1-02)

Set-Point Preset

(H1-03 = 80)

S 5 (H1-03)

Fixed Speed Auto

(H1-05 = 86)

S 7 (H1-05)

S N

M 1

M 2

(H2-01)

Digi tal
O utput 1

During Run 1
(H2-2 = 0)

i QP um p

S1

A 2 (4-20mA )

S3 (H1-01)

S4 (H1-02)

S5 (H1-03)

S7 (H1-05)

SN

Run

Pressure Feedback

(H3-09 = B )

Pump Fault

(H1-01 = 24)

Fault Reset

(H1-02 = 14)

Set-Point Preset

(H1-03 = 80)

M 1

M 2

M 3

M 4

P1-01 = 1 : Drive + 1 Pump

P1-01 = 0 : Drive only
H2-01 = 0 : During RUN 1

Figure 5.28

M 1

Pump 2 Control

(H2-01 = 40)

(H2-01 = 5)

L4-01 = Must be greater than P1-06

Frequency Detection 2

H2-01 = 5: Frequency Detection 2

L4-02 = 2.0 Hz