Yaskawa iQpump Programming Manual User Manual

Page 80

Advertising
background image

80

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

Terminal Signal Level Selections

When the iQpump drive is equipped with the optional, removable terminal board with 4-20 mA outputs (p/n ETC618120), parameters

H4-07 and H4-08 determine whether analog outputs are configured as 0-10 Vdc or 4-20 mA. Refer to the documentation for the optional

terminal board as the proper jumper settings are required in addition to programming H4-07 and H4-08.

If the standard removable terminal board is being used, the settings of H4-07 and H4-08 have no effect.

Parameter No.

Setting

Description

H4-07

0

Terminal FM Signal Level Selection, 0 - 10 Vdc (factory default)

H4-08

1

Terminal AM Signal Level Selection, 4 - 20 mA

Advertising