P5 Pump Protection

P5-01 Hand Mode Reference

The iQpump drive can be operated manually or in the “Hand” mode. The frequency for the hand mode can be an analog input (0 ~ 10

Vdc) or from the digital operator (P5-02).

The hand mode operation is useful when testing the system during initial start-up without the automated regulation functions of the

iQpump drive.

The selection to determine the hand mode reference is determined by programming the Hand Mode Reference Source (P5-01). If P5-01 =

1, then the hand reference frequency is set by programming the Hand Reference (P5-02).

The Hand Mode Reference Source (P5-01) works in conjunction with the Hand Reference (P5-02) if P5-01 = 1.

The Hand Mode can be activated from the digital operator or by programming a multi-function digital input for “Hand Mode” (H1-xx =

80).

Note: To change the hand reference requires the P5-02 parameter to be programmed also. U1-01 will be the only monitor

available and the Up/Down arrow keys will not operate like a digital MOP.

Hand Mode Operation from Keypad (Factory Default)

Figure 1.129

Figure 134

Hand Mode Operation from External Signal (P5-01 = 0)

Connection Diagram of Potentiometer

Figure 1.130

Figure 135

Setting

Description

0

Analog Input A1 (0~10 V)

1

Hand Reference (P5-02)

(factory default)