L8-11 Heatsink Cooling Fan Operation Delay Time

<0033>

Setting Range:

0 to 300 sec

Factory Default: 300 sec

Parameters L8-10 and L8-11 allow the iQpump drive programmer to customize the heatsink cooling fan operation. Parameter L8-10

determines whether the cooling fans are always ON whenever the iQpump drive is powered (L8-10 = “1: Fan Always On”) or if the

cooling fans are only ON when the iQpump drive is in a Run condition (L8-10 = “0: Fan On-Run Mode”).

Parameter L8-11 is a delayed OFF for the cooling fan if L8-10 = “0: Fan On-Run Mode”. When the cooling fans are set to turn OFF is

when either the Run command is removed or the drive is in baseblock. The iQpump parameter L8-11 will cause the fans to continue

cooling the iQpump drive for the amount of time programmed into L8-11 after the Run command is actually removed or baseblocked

enabled. The iQpump drive can be programmed to allow the cooling fan to run for up to 5 minutes (factory default) after the run

command is removed or baseblock enabled.

Both parameters are intended to extend fan life while still providing sufficient cooling for proper iQpump drive operation.

Figure 1.94

Figure 99 Heatsink Cooling Fan Operation Timing Diagram

L8-12 Ambient Temperature Setting

Setting Range:

113 to 140

°F (45 to 60°C)

Factory Default: 113

°F (45°C)

Set parameter L8-12 to the temperature

°F (°C) of the area in which the iQpump drive is mounted. If L8-12 exceeds the actual rated

ambient temperature of the iQpump drive 113

°F (45°C), the OL2 fault level will be de-rated as shown in the figure below. This will allow

the user to trade-off lighter drive loading for operation in a higher ambient temperature.

Figure 1.95

Figure 100 Ambient Temperature Derating Curve

L8-15 OL2 Characteristic Selection at Low Speeds

At very low speeds (6 Hz and below) and very high current levels it can be possible to damage output transistors. Therefore the factory

default setting of L8-15 is to shorten the time before an OL2 fault will occur during low speed/high load situations (L8-15 = “1:

Enabled”).

Setting

Description

0

Disabled

1

Enabled (L8-18 is active) (factory default)

TIME

OFF (OPEN)

ON (CLOSED)

OFF (OPEN)

ON (CLOSED)

OR

BaseBlock

OFF (OPEN)

ON (CLOSED)

0

80%

100%

45

o

C

60

o

C

Ambient Temp.

(L8-12)

OL2 Rating

OL2 Fault Level

113

o

F

(45

o

C)

(60

o

C)

140

o

F