P3-09 pump 2 frequency shutdown level, P3-10 pump 3 frequency shutdown level – Yaskawa iQpump Programming Manual User Manual

Page 153

Advertising
background image

YASKAWA TM.iQp.02 iQpump Drive Programming Manual

153

Figure 1.116

Figure 121

P3-09 Pump 2 Frequency Shutdown Level

Setting Range:

0.0 to 120.0 Hz

Factory Default: 35.0 Hz

The Pump 2 shutdown frequency level used for the multiplex pumping operation (de-staging) is programmed in the Pump 2 Frequency

Shutdown Level (P3-09). The Pump 2 Frequency Shutdown Level (P3-09) is active when the Lead-Lag Control (P3-01) is set to 0 or 2.

The multiplex pumping operation (de-staging) is determined by the programmed setting of P3-01 as described below.

If P3-01 = 0: Output Frequency

The de-staging (turning OFF) of the auxiliary pump occurs when the output frequency falls below the Pump 2 Frequency Shutdown

Level (P3-09) for the time programmed in the Shutdown Pump Delay Time (P3-06).

The auxiliary pumps will be removed by the control of the multi-function digital output contact opening (H2-xx = 40 and 41).

If P3-01 = 1: Feedback Level (P3-02: Not Used)

The Pump 2 Frequency Shutdown Level (P3-09) is not used when Lead-Lag Control (P3-01) is set to 1.

If P3-01 = 2: Output Frequency + Feedback Level

The de-staging (turning OFF) of the auxiliary pump occurs when the output frequency falls below the Pump 2 Frequency Shutdown

Level (P3-09) and the difference between the feedback minus the system’s setpoint has exceeded the Shutdown Pump Delta Level (P3-

05) for the time programmed in the Shutdown Pump Delay Time (P3-06).

The auxiliary pumps will be removed by the control of the multi-function digital output contact opening (H2-xx = 40 and 41).

Refer to Lead-Lag Control (P3-01) for further description of the de-staging of the pump system.

P3-10 Pump 3 Frequency Shutdown Level

Setting Range:

0.0 to 120.0 Hz

Factory Default: 35.0 Hz

The Pump 3 shutdown frequency level used for the multiplex pumping operation (de-staging) is programmed in the Pump 3 Frequency

Shutdown Level (P3-10). The Pump 3 Frequency Shutdown Level (P3-10) is active when the Lead-Lag Control (P3-01) is set to 0 or 2.

The multiplex pumping operation (de-staging) is determined by the programmed setting of P3-01 as described below.

If P3-01 = 0: Output Frequency

The de-staging (turning OFF) of the auxiliary pump occurs when the output frequency falls below the Pump 3 Frequency Shutdown

Level (P3-10) for the time programmed in the Shutdown Pump Delay Time (P3-06).

The auxiliary pumps will be removed by the control of the multi-function digital output contact opening (H2-xx = 40 and 41).

Time

SET-POINT

Set-Point - 2 x P3-08

Set-Point - P3-08

PUMP 1

PUMP 1 + 2

PUMP 1 + 2 + 3

PUMP 1 + 2

Set-Point - P3-08

PUMP 1