b4 Delay Timers

The iQpump drive has an internal timer function that operates independently from the Drive. A digital input must be programmed to be a

timer start input by setting H1-0x = 18. A digital output must be programmed as a timer output by setting H2-0x = 12. (Not to be

confused with the “Wait to Run Time” in b1-11.)

b4-01 Timer Function ON-Delay Time

Setting Range:

0.0 to 3000.0 sec

Factory Default: 0.0 sec

The timer start input (H1-0x = 18) must be held on for at least the time specified in parameter b4-01 before the digital output programmed

as the timer output will close. See

Figure 20

for timing details.

b4-02 Timer Function OFF-Delay Time

Setting Range:

0.0 to 3000.0 sec

Factory Default: 0.0 sec

The timer start input (H1-0x = 18) must be held off for at least the time specified by b4-02 before the digital output programmed as the

timer output will open. See

Figure 20

for timing details.

Figure 1.20

Figure 20 Timing Diagram of Timer Function

Multi-function Contact
Input: Timer Function

Multi-function Contact

Output: Timer Function

b4-01

b4-01

b4-02

ON (CLOSED)

OFF (OPEN)

ON (CLOSED
OFF (OPEN)

b4-02