YASKAWA TM.iQp.02 iQpump Drive Programming Manual

97

Figure 1.82

Figure 87 Motor Overload Protection Time based on Output frequency and Load

L1-03 Motor Overheat Alarm Operation Selection

L1-04 Motor Overheat Fault Operation Selection

L1-05 Motor Temperature Input Filter Time

Setting Range:

0.00 to 10.00 sec

Factory Default: 0.20 sec

The iQpump drive can be programmed to accept a PTC (Positive Temperature Coefficient) Thermistor input for monitoring motor

temperature. By setting parameter H3-09 = “E: Motor Temperature,” and attaching the PTC thermistor per the figure below, the iQpump

drive can react to the increasing motor winding temperature with both an alarm (L1-03) and a fault (L1-04).

Setting

Description

0

Ramp to Stop

1

Coast to Stop

2

Fast-Stop

3

Alarm Only (

factory default)

Setting

Description

0

Ramp to Stop

1

Coast to Stop (

factory default)

2

Fast-Stop

125%

4

2

Time

(M

inut

es

)

Output Current

(Percent of motor FLA)

E2-01 200%

6

8

10

60Hz

10Hz

175%

150%