TM.iQp.02 iQpump Drive Programming Manual

H5-09

0435H

Communication Error
Detection Time
CE Detect Time

Determines how long communications must be lost before a fault is
annunciated. Works in conjunction with parameters H5-05 and H5-04.

0.0 to 10.0
(H5-08=0)
0.0 to 10.0
(H5-08=1)
0.0 to 90.0
(H5-08=2)

2.0 sec

Programming

94

Motor Overload

L1-01

0480H

Motor Overload
Protection Selection
MOL Fault Select

Enables or disables the motor thermal overload protection.
0: Disabled
1: Std Fan Cooled (Enabled)
2: Std Blower Cooled
3: Vector Motor

0 to 1

1

Programming

96

L1-02

0481H

Motor Overload
Protection Time
MOL Time Const

Determines how much time will elapse prior to a motor overload fault
(OL1), when motor amps exceed the value set in parameter E2-01 by
10%. Actual (OL1) trip time will vary depending on severity of
overload.

0.1 to 20.0

8.0min

Programming

96

L1-03

0482H

Motor Overheat Alarm
Operation Selection
Mtr OH Alarm Sel

Operation selection when the motor temperature analog input
(H3-09 = E) exceeds the OH3 alarm level (1.17 V)
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

Programming

97

L1-04

0483H

Motor Overheat Fault
Operation Selection
Mtr OH Fault Sel

Stopping method when the motor temperature analog input
(H3-09 = E) exceeds the OH4 level (2.34 V).
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop

0 to 2

1

Programming

97

L1-05

0484H

Motor Temperature Input
Filter Time
Mtr Temp Filter

Delay Time applied to motor temperature analog input (H3-09 = E) for
filtering purposes.

0.00 to

10.00

0.20 sec Programming

97

PwrLoss Ridethru

L2-01

0485H

Momentary Power Loss
Detection Selection
PwrL Selection

Enables and disables the momentary power loss function.
0: Disabled - Drive trips on (UV1) fault when power is lost.
1: PwrL Ride Thru t - Drive will restart if power returns within the time
set in L2-02.*
2: CPU Power Active - Drive will restart if power returns prior to
internal power supply shut down.*
* In order for a restart to occur, the run command must be maintained
throughout the ride thru period.

0 to 2

2

Programming

99

L2-02

0486H

Momentary Power Loss
Ride-thru Time
PwrL Ridethru t

Determines the power loss ride-thru time. This value is dependent on
the capacity of the Drive. Only effective when L2-01 = 1.

0.0 to 25.5

sec

kVA

Dependent

Programming

99

L2-03

0487H

Momentary Power Loss
Minimum Base Block
Time
PwrL Baseblock t

Used to allow the residual motor voltage to decay before the Drive
output turns back on. After a power loss, if L2-03 is greater than L2-02,
operation resumes after the time set in L2-03.

0.1 to 5.0

sec

kVA

Dependent

Programming

99

L2-04

0488H

Momentary Power Loss
Voltage Recovery Ramp
Time
PwrL V/F Ramp t

The time it takes the output voltage to return to the preset V/f pattern
after speed search (current detection mode) is complete.

0.0 to 5.0

sec

kVA

Dependent

Programming

100

L2-05

0489H

Undervoltage Detection
Level
PUV Det Level

Sets the Drive's DC Bus undervoltage trip level. If this is set lower than
the factory setting, additional AC input reactance or DC bus reactance
may be necessary.

Voltage

Class

Dependent

Voltage

Class

Dependent

Programming

100

Stall Prevention

L3-01

048FH

Stall Prevention
Selection During Accel
StallP Accel Sel

0: Disabled (Motor accelerates at active acceleration, C1-01 or C1-03.
The motor may stall if load is too heavy or accel time is too short.)
1: General Purpose (When output current exceeds L3-02 level,
acceleration stops. It starts to accelerate at current value recovery.)
2: Intelligent (The active acceleration rate, C1-01 or C1-02, is ignored.
Acceleration is completed in the shortest amount of time w/o
exceeding the current value set in L3-02.

0 to 2

1

Programming

101

L3-02

0490H

Stall Prevention Level
During Accel
StallP Accel Lvl

This function is enabled when L3-01 is “1” or “2”. Drive rated current
is 100%. Decrease the set value if stalling occurs at factory setting.

0 to 200

120%

Programming

101

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page