Yaskawa iQpump Programming Manual User Manual

Page 184

Advertising
background image

184

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

H2-02

(continued)

040CH

Terminal M3-M4
Function Selection
Term M3-M4 Sel

42: Pump Fault
Function Active in hand, auto, pre-charge and thrust mode
Open: No Dedicated Pump Faults are active.
Closed: Dedicated pump fault active (Low Feedback Fault, High
Feedback Fault, Over Cycling Fault, Pump Protection Fault,
Thermostat Fault, Low Water Fault, Ext. Pump Fault).

0 to 42

41

Programming

63

Analog Inputs

H3-02



0411H

Terminal A1 Gain Setting
Terminal A1 Gain

Sets the speed command when 10 V is input, as a percentage of the
maximum output frequency (E1-04).

0.0 to

1000.0

100.0% Programming

70

H3-03



0412H

Terminal A1 Bias Setting
Terminal A1 Bias

Sets the speed command when 0 V is input, as a percentage of the
maximum output frequency (E1-04).

–100.0 to

+100.0

0.0%

Programming

70

H3-08

0417H

Terminal A2 Signal
Level Selection
Term A2 Signal

Selects the signal level of terminal A2.
0: 0 - 10 Vdc (switch S1-2 must be in the off position)
2: 4 - 20 mA (switch S1-2 must be in the on position)

0 or 2

2

Programming

71

H3-09

0418H

Aux Terminal Function
Selection
Terminal A2 Sel

Selects what effect the aux terminal has on the Drive.
0: Frequency Bias - 0 - 100% bias
2: Aux Reference
B: PI Feedback
D: Frequency Bias 2 - 0 - 100% bias
E: Motor Temperature - See parameters L1-03 & L1-04
16: PI Differential
1F: Not Used

0 to 1F

B**

Programming

72

H3-10



0419H

Terminal A2 Gain Setting
Terminal A2 Gain

Sets the percentage when 10 V (20 mA) is input.

0.0 to

1000.0

100.0% Programming

76

H3-11



041AH

Terminal A2 Bias Setting
Terminal A2 Bias

Sets the percentage when 0 V (4 mA) is input.

–100.0 to

+100.0

0.0%

Programming

76

H3-12

041BH

Analog Input Filter Time
Constant Filter Avg Time

Used to “smooth” out erratic or noisy analog input signals.

0.00 to

2.00

0.30 sec Programming

76

H3-13

041CH

Master Frequency
Reference

Terminal SelectionTA1/
A2 Select

Determines which terminal will be the main reference source.
0: Main Fref TA1 - Terminal TA1 is the main speed command and
Terminal TA2 is the Aux speed command.
1: Main Fref TA2 - Terminal TA2 is the main speed command and
Terminal TA1 is the Aux speed command. Only effective when H3-09
is set to 2 “Aux Reference”.

0 or 1

0

Programming

76

 Denotes that parameter can be changed when the drive is running.
** Factory setting changes to “B” when b5-01 = 1.

Analog Outputs

H4-01

041DH

Terminal FM Monitor
Selection
Terminal FM Sel

Selects which monitor will be output on terminals FM and AC.
1: Frequency Ref (100% = max. output frequency)
2: Output Freq (100% = max. output frequency)
3: Output Current (100% = Drive rated current)
6: Output Voltage (100% = 230 V or 100% = 460 V)
7: DC Bus Voltage (100% = 400 V or 100% = 800 V)
8: Output kWatts (100% = Drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100% = Motor rated secondary current)
20: SFS Output (100% = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100% = max. output frequency)
38: PI Setpoint

Note:

100% = 10 V DC output * FM gain setting (H4-02).

1 to 38

<0032>

2

Programming

77

H4-02



041EH

Terminal FM Gain
Setting
Terminal FM Gain

Sets terminal FM output voltage (in percent of 10 V) when selected
monitor is at 100% output.

0.0 to

1000.0

100.0% Programming

78

H4-03



041FH

Terminal FM Bias
Setting
Terminal FM Bias

Sets terminal FM output voltage (in percent of 10 V) when selected
monitor is at 0% output.

–110.0 to

110.0

0.0%

Programming

78

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.