YASKAWA TM.iQp.02 iQpump Drive Programming Manual

19

Parameter b2-04 also serves the function of affecting the length of time DC Injection to stop (b1-03 = “2: DC Injection to Stop”) will

occur.

b2-09 Motor Pre-Heat Current

Setting Range:

0 to 100%

Factory Default: 0%

A DC current can be circulated within the motor windings while the motor is stopped. The current will produce heat within the motor and

prevent condensation. Parameter b2-09 determines the percentage of the iQpump drive rated output current that will be used for the

motor pre-heat function. This function can be useful in applications where the motor sits for extended periods of time in humid

conditions. Motor pre-heating can only be initiated by closing a digital input programmed as a Motor Pre-heat Input (H1-0x = 60). Check

with the motor manufacturer to determine the maximum acceptable current level the motor can withstand when stopped. Be sure not to

exceed the motor manufacturers recommended level.