Yaskawa iQpump Programming Manual User Manual

Page 106

Advertising
background image

106

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

• OL1 (Motor Overload)

• OL3 (Overtorque)

• OL2 (Drive Overload)

• OV (DC Bus Overvoltage)

• GF (Ground Fault)

• UV1 (DC Bus Undervoltage)

• OH1 (Overheat)

In order for auto restart after a UV1 fault, Momentary Power Loss Ride-thru must be enabled (L2-01 = “1: PwrL Ride Thru t,” or “2:

CPU Power Active”). Setting H2-01 or H2-02 equal to “1E” configures a digital output as “Restart Enabled” to signal if an impending

auto restart is possible.